TABLE 33 – ISN OPERATIONAL AND FAULT CODES
P56/58
OPERATIONAL CODE
0
NO ABNORMAl CONDITION
1
UNIT SWITCh OFF
2
SySTEM SWITCh OFF
3
lOCK-OUT
4
UNIT FAUlT
5
SySTEM FAUlT
6
REMOTE ShUTDOWN
7
DAIly SChEDUlE ShUTDOWN
8
NO RUN PERMISSIVE
9
NO COOl lOAD
10
ANTI-COINCIDENCE TIMER ACTIVE
11
ANTI-RECyClE TIMER ACTIVE
12
MANUAl OVERRIDE
13
SUCTION lIMITING
14
DISChARGE lIMITING
15
CURRENT lIMITING
16
lOAD lIMITING
17
COMPRESSOR(S) RUNNING
18
hEAT PUMP lOAD lIMITING
JOHNSON CONTROLS
ISN CONTROL (CON'T)
P57/59
0
NO FAUlT
1
VAC UNDER VOlTAGE
2
lOW AMBIENT TEMPERATURE
3
hIGh AMBIENT TEMPERATURE
4
lOW lEAVING ChIllED lIQUID TEMP
5
hIGh DISChARGE PRESSURE
6
hIGh DIFFERENTIAl OIl PRESSURE
7
lOW SUCTION PRESSURE
8
hIGh MOTOR CURRENT
9
llSV NOT ON
10
lOW BATTERy WARNING
11
hIGh OIl TEMPERATURE
12
hIGh DISChARGE TEMPERATE
13
IMPROPER PhASE ROTATION
14
lOW MOTOR CURRENT /MP / hPCO
15
MOTOR CURRENT UNBAlANCED
16
lOW DIFFERENTIAl OIl PRESSURE
17
GROUND FAUlT
18
MP /hPCO
19
lOW EVAPORATOR TEMPERATURE
20
INCORRECT REFRIGERANT PROGRAMMED
21
POWER FAIlURE, MANUAl RESET
REQUIRED
22
UNIT MOTOR CURRENT
23
lOW SUPERhEAT
24
SENSOR FAIl
25
DISChARGE INhIBIT
26
MP/hPCO INhIBIT
27
PUMP TRIP
28
PUMP FAIl MAKE FlOW
SECTION 10 - MAINTENANCE
FAULT CODE
10
159

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ycal0018ecYcal0021ecYcal0025ecYcal0027ecYcal0032ec