FILTER
ACCESS
DOOR
RETURN
DUCT
FILTER
SUPPORT
BRACKET
(Field Supplied)
AIR FLOW
Possible Upright Counterflow Filter Locations
Horizontal Installations
Filters must be installed in either the central return regis-
ter or in the return air duct work.
Startup Procedure & Adjustment
Furnace must have a 115 VAC power supply properly
connected and grounded. Proper polarity must be main-
tained for correct operation. In addition to the following
start-up and adjustment items, refer to further informa-
tion in Operational Checks section.
100%
IGNITION
(80%)
78%
57%
2 MINS.
MIN.
Operation with Conventional 1-Stage Thermostat
(DIP switch selects 1-Stage heat)
Call for heat, thermostat energizes W1 on the furnace
control board (W2 input is ignored).
After a successful Light Off Sequence and expiration of
the Ignition Stabilization Period:
•
The furnace control board adjusts the firing rate to
35% (low fire rate).
CENTRAL
RETURN
GRILLE
Figure 44
UNIT CALL FOR HEAT ENDS
10 MINS.
8 MINS.
Figure 45
•
After 2 minutes, the furnace control board increases
the firing rate to 57% at a rate of 1% per second.
•
After 10 total minutes, the furnace control board
increases the firing rate to 78% at a rate of 1% per
second.
•
After 20 total minutes, the furnace control board
increases to 100% at a rate of 1% per second for the
remainder of the call for heat.
•
The circulator fan is adjusted to the appropriate CFM,
corresponding to the current firing rate.
IGNITION
(80%)
70%
60%
50%
2 MINS.
MIN.
Operation with Conventional 2-Stage Thermostat
(DIP switch selects 2-stage heat)
Call for 1st-Stage Heat - Thermostat contacts close R to
W1.
After a successful Light Off Sequence and expiration of
the Ignition Stabilization Period:
•
The furnace control board adjusts to the low firing
rate.
•
After 2 minutes, the furnace control board increases
the firing rate to 50% for the next 8 minutes.
•
Thereafter, the furnace control board will increase
the firing rate 10%, at a rate of 1% per second, every
10 minutes for the remainder of the call for heat (See
above figure).
•
The circulator fan is adjusted to the appropriate CFM,
corresponding to the current firing rate.
90%
IGNITION
(80%)
70%
60%
50%
2 MINS.
MIN.
Operation with Conventional 2-Stage Thermostat
(DIP switch selects 2-stage heat)
10 MINS.
8 MINS.
Figure 46
10 MINS.
8 MINS.
Figure 47