Use a separate fused branch electrical circuit containing
properly sized wire, and fuse or circuit breaker. The fuse
or circuit breaker must be sized in accordance with the
maximum overcurrent protection specified on the unit
rating plate. An electrical disconnect must be provided at
the furnace location.
Connect hot, neutral, and ground wires as shown in the
wiring diagram located on the unit's blower door. For
direct vent applications, the cabinet opening to the
junction box must be sealed air tight using either an UL
approved bushing such as Heyco Liquid Tight or by apply-
ing non-reactive UL approved sealant to bushing.
Line polarity must be observed when making field con-
nections. Line voltage connections can be made through
either the right or left side panel. The furnace is shipped
configured for a right side (left side for counterflows)
electrical connection with the junction box located inside
the burner compartment. To make electrical connections
through the opposite side of the furnace, the junction
box must be relocated to the other side of the burner
compartment prior to making electrical connections. To
relocate the junction box, follow the steps shown below.
NOTE: Wire routing must not interfere with circulator
blower operation, filter removal, or routine maintenance.

Junction Box Relocation

E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK
DISCONNECT ELECTRICAL POWER BEFORE INSTALLING OR SERVICING THIS
.
UNIT
HIGH VOLTAGE !
T
O AVOID THE RISK OF INJURY
,
DEATH
THE FURNACE MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN
,
THEIR ABSENCE
WITH THE LATEST EDITION OF THE
N
E
C
. US: National Electrical
ATIONAL
LECTRIC
ODE
Code (NEC) ANSI/NFPA 70-2011. In CANADA:
Canadian Electrical Code CSA C22.1.
Line voltage connections can be made through either the
right or left side panel. The furnace is shipped configured
for a right side electrical connection. To make electrical
connections through the opposite side of the furnace, the
junction box must be relocated to the left side prior to
making electrical connections. To relocate the junction
box, perform the following steps.
WARNING
. U
SE GLOVES AS A
.
WARNING
WARNING
,
ELECTRICAL SHOCK OR
1. Remove the burner compartment door.
2. Remove and save the two screws securing the junc-
tion box to the side panel.
3. Relocate junction box and associated plugs and
grommets to opposite side panel. Secure with screws
removed in step 2.
T
O AVOID THE RISK OF INJURY
FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH
LOCAL CODES OR
E
NATIONAL
LECTRICAL
To ensure proper unit grounding, an earth ground wire
must be connected between the furnace ground screw
located inside the furnace junction box and the electrical
service panel. NOTE: Do not use gas piping as an electri-
cal ground. To confirm proper unit grounding, turn off the
electrical power and perform the following check.
1. Measure resistance between the neutral (white) con-
nection and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock
switch which interrupts unit voltage when the blower
door is opened for servicing. Do not defeat this switch.

24 Volt Thermostat Wiring

W
IRE ROUTING MUST NOT INTERFERE WITH CIRCULATOR BLOWER
,
OPERATION
FILTER REMOVAL OR ROUTINE MAINTENANCE
A
REMOVABLE PLUG CONNECTOR IS PROVIDED WITH THE FURNACE
CONTROL TO MAKE THERMOSTAT WIRE CONNECTIONS
,
BE REMOVED
WIRE CONNECTIONS MADE TO THE PLUG
. I
REPLACED
T IS
,
BE JOINED WITH A WIRE NUT AND A SINGLE CONDUCTOR BE INSERTED
UNDER THE TERMINAL SCREW
INTERMITTENT OPERATION
HEAT SET-UP DIP SWITCH
MATCH THERMOSTAT TYPE
, DIP
THERMOSTAT
ALSO THE CORRECT SETTING FOR A NON
. T
THERMOSTAT
O USE
MODULATING THERMOSTAT
OFF
IN THE
POSITION
POSITION WHEN USING A NON
.
THERMOSTAT
When installed with a non-communicating thermostat,
the furnace integrated control module provides terminals
for both "W1" and "W2", and "Y1" and "Y2" thermostat
connections.
WARNING
,
ELECTRICAL SHOCK OR DEATH
,
,
IN THEIR ABSENCE
WITH THE LATEST EDITION OF THE
C
.
ODE
STRONGLY
RECOMMENDED THAT MULTIPLE WIRES
. F
AILURE TO DO SO MAY RESULT IN
.
IMPORTANT NOTE
-
DIP
#13 MUST
SWITCH
. T
CTK01
O USE THE
#13
SWITCH
MUST BE SET TO
-
COMMUNICATING
CTK02**, CTK03**
OR
,
CHECK TO MAKE SURE
(
). T
FACTORY POSITION
HIS IS ALSO THE CORRECT
-
COMMUNICATING SINGLE
,
THE
.
. T
HIS PLUG MAY
,
AND
BE SET TO
COMMUNICATING
ON
. T
POSITION
HIS IS
2-
STAGE
CTK04**
DIP
#13
SWITCH
IS
-
STAGE