Carrier 40VMH024 Installation And Maintenance Instructions Manual page 25

High static ducted indoor unit for variable refrigerant flow (vrf) systems
Table of Contents

Advertisement

Side view of fan assembly
installation state
Push fan assembly
horizontally to the end
(about 71in), and
then take off it.
1. Remove all 12 screws from the Safety Drain Tray, and remove the safety drain tray. See Fig. 41.
2. Remove all 4 bolts from the fan assembly. See Fig. 42.
3. Horizontally push the fan assembly until it cannot not move any further, and lift up slightly, and take down to remove. See Fig. 42.
4. After the motor maintenance is complete, reinstall the fan assemblies, and connect the motor with electric control box.
Scroll
Move 18mm
Fig. 42 —Fan Disassembly (048-054)
Front view of fan assembly installation
Fan assembly is taken off
25
Pothook
Move