Mode
Description
Out of Service (OOS)
The functions performed by the block will not execute. If the block has
any outputs, these will typically not update and the status of any values
passed to other blocks is "BAD". Before you change the configuration of
the block, change the mode of the block to OOS. When the changes are
complete, change the mode back to Auto.
Mode parameters
Mode parameters change the block mode from one state to another. For example, you
may want to change from Auto mode to Out of Service.
In the resource and transducer blocks, the mode parameters are often in the Process
menu. In all other function blocks, the parameters are in the Common Config menu.
Mode
Target
Actual
Permitted
Normal
Change the block mode for a FOUNDATION fieldbus device
Whenever you need to change the parameters or properties of a block, change the mode.
You can change the mode for a block from the Block List, or you can open a specific block
and change the mode.
Procedure
1. Connect to a FOUNDATION fieldbus device.
2. To change the modes for one or more blocks on the Block List:
a) Tap the mode button on the Block List.
A list of all blocks and the selected modes is displayed.
b) For each block in the list you want to modify, select the block and select the
desired mode.
c) Tap OK.
d) Tap Send.
e) Review the changes.
f) Tap Send.
3. To change the mode from within a block:
www.
Description
The mode that is assigned to a block and is used to change a block to
a desired mode.
The current mode of the block.
The modes that are allowed for a block. Setting the Permitted modes
prevents unauthorized changes to the operating mode of a block. To
do this, configure the Block:Mode Permitted parameter to allow only
the desired operating modes. It is recommended to always select
OOS as one of the Permitted modes.
The mode that the block should be set to during normal operation
conditions.