Turn off this output (oFF).
Select PID Control Mode (PId) for this output (factory default). PID parameters are
set outside the specific output submenus, as more than one output can be used for
PID control at a time. See
Select On/Off Control Mode (oN.oF) for this output. More than one output can be
set up for oN.oF control. For Heat / Cool control set the output connected to the
heater with ACtN equal to RVRS and the output connected to the cooling device
with ACtN set to dRCt.
Navigate to the desired setting. Settings include the following:
Select the indicated setting.
For ACtN, select the correct setting. Settings include the following:
For dEAd, set the desired value. (The default is 5.0.)
Select the indicated ACtN setting, or confirm the dEAd value.
Select this Output to be an Alarm using the Alarm 1 (ALM.1) configuration.
5.4.1.1
Turn Off Output Channel (PRoG > oUt1–oUt3 >
ModE > oFF)
5.4.1.2
PID Control Mode (PRoG > oUt1–oUt3 > ModE >
PId)
5.5 PID Configuration (PRoG >
5.4.1.3
On/Off Control Mode (PRoG > oUt1–oUt3 >
ModE > oN.oF)
ACtN – Determines the action direction for control
dEAd – Sets the deadband value; the deadband value is applied in the
same units as the process variable to one side of Setpoint as determined by
the ActN direction
S.PNt – Allows either Setpoint 1 or Setpoint 2 to be specified as the
target value; Setpoint 2 can be set to track Setpoint 1 using the deviation
(dEVI) option
(5.2 Setpoint 2 (PRoG >
up for heat/cool operation
RVRS – Off when Process Value is > Setpoint, and on when Process Value
is < Setpoint (e.g., heating); deadband is applied below Setpoint (factory
default)
dRCt – Off when Process Value is < Setpoint, and on when Process Value
is > Setpoint (e.g., cooling); deadband is applied above Setpoint
5.4.1.4
Output as Alarm 1 (PRoG > oUt1–oUt3 > ModE >
ALM.1)
Reference Section: Programming Mode (PRoG)
PID).
SP2))—a useful feature when setting