Page 1
Products Solutions Services KA01406D/06/EN/01.18 71415025 2018-11-01 Brief Operating Instructions Proline 500 PROFIBUS PA Transmitter with electromagnetic sensor These instructions are Brief Operating Instructions; they are not a substitute for the Operating Instructions pertaining to the device. Transmitter Brief Operating Instructions Contain information about the transmitter.
Page 2
Proline 500 PROFIBUS PA Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
Page 3
These Brief Operating Instructions are the Transmitter Brief Operating Instructions. The "Sensor Brief Operating Instructions" are available via: • Internet: www.endress.com/deviceviewer • Smart phone/tablet: Endress+Hauser Operations App Detailed information about the device can be found in the Operating Instructions and the other documentation: • Internet: www.endress.com/deviceviewer...
Proline 500 PROFIBUS PA About this document About this document Symbols used 1.1.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation.
Page 6
About this document Proline 500 PROFIBUS PA Symbol Meaning Protective Earth (PE) A terminal which must be connected to ground prior to establishing any other connections. The ground terminals are situated inside and outside the device: • Inner ground terminal: Connects the protectiv earth to the mains supply.
Proline 500 PROFIBUS PA Basic safety instructions Basic safety instructions Requirements for the personnel The personnel must fulfill the following requirements for its tasks: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task. ‣...
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
Proline 500 PROFIBUS PA Basic safety instructions IT security Our warranty is valid only if the device is installed and used as described in the Operating Instructions. The device is equipped with security mechanisms to protect it against any inadvertent changes to the settings.
Product description Proline 500 PROFIBUS PA Product description The measuring system consists of a Proline 500 transmitter and an electromagnetic Proline Promag sensor. The transmitter and sensor are mounted in physically separate locations. They are interconnected via two connecting cable.
Proline 500 PROFIBUS PA Installation Installation For detailed information about mounting the sensor, see the Sensor Brief Operating Instructions → 3 Mounting the transmitter housing CAUTION Ambient temperature too high! Danger of electronics overheating and housing deformation. ‣ Do not exceed the permitted maximum ambient temperature .
Page 12
Installation Proline 500 PROFIBUS PA 4.1.2 Post mounting 20 70 … ( 0.79 to 2.75) SW 13 A0029057 2 Engineering unit mm (in) Endress+Hauser...
Proline 500 PROFIBUS PA Installation Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned. – – 3 mm 4 mm A0029993 Depending on the device version: Loosen the securing clamp of the connection compartment cover.
Installation Proline 500 PROFIBUS PA Turning the display module The display module can be turned to optimize display readability and operability. – – – 3 mm A0030035 Depending on the device version: Loosen the securing clamp of the connection compartment cover.
Proline 500 PROFIBUS PA Installation Transmitter post-installation check The post-installation check must always be performed after the following tasks: • Mounting the transmitter housing: – Post mounting – Wall mounting • Turning the transmitter housing • Turning the display module Is the device undamaged (visual inspection)? ...
Electrical connection Proline 500 PROFIBUS PA Electrical connection NOTICE The measuring device does not have an internal circuit breaker. ‣ For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
Page 17
Proline 500 PROFIBUS PA Electrical connection Signal cable PROFIBUS PA Twisted, shielded two-wire cable. Cable type A is recommended . For further information on planning and installing PROFIBUS networks see: • Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning"...
Page 18
Electrical connection Proline 500 PROFIBUS PA Cable length (max.) Depends on the medium conductivity, max. 200 m (656 ft) Cable lengths (available for 5 m (15 ft), 10 m (32 ft), 20 m (65 ft) or variable length up to max. 200 m (656 ft)
Page 19
Proline 500 PROFIBUS PA Electrical connection 5.1.4 Terminal assignment Transmitter: supply voltage, input/outputs The terminal assignment of the inputs and outputs depends on the individual order version of the device. The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
Page 20
Electrical connection Proline 500 PROFIBUS PA If the measuring device is supplied with cable glands: Observe requirements for connecting cables → 16. 5.1.7 Preparing the connecting cable When terminating the connecting cable, pay attention to the following points: In the case of the electrode cable: Make sure that the ferrules do not touch the core shields on the sensor side.
Page 21
Proline 500 PROFIBUS PA Electrical connection Preparing the connecting cable: Promag H Transmitter Electrode cable Coil current cable 70 (2.76) 80 (3.15) 50 (1.97) 17 (0.67) 50 (1.97) 8 (0.3) 10 (0.4) 8 (0.3) A0029544 A0029543 Engineering unit mm (in)
Page 22
Electrical connection Proline 500 PROFIBUS PA Sensor Electrode cable Coil current cable 70 (2.76) 80 (3.15) 17 (0.67) 40(1.57) 8 (0.31) 8 (0.31) ≥ 1 (0.04) A0029438 A0029439 Engineering unit mm (in) A = Terminate the cable B = Fit ferrules on cables with fine-wire cores (stranded cables) 1 = Red ferrules, ...
Page 23
Proline 500 PROFIBUS PA Electrical connection Preparing the connecting cable: Promag P and Promag W Transmitter Electrode cable Coil current cable (3.54) 100 (3.94)* 70 (2.76) 80 (3.15) 50 (1.97) 17 (0.67) 50 (1.97) 8 (0.3) 10 (0.4) 8 (0.3)
Proline 500 PROFIBUS PA Electrical connection Connecting the measuring device NOTICE Limitation of electrical safety due to incorrect connection! ‣ Have electrical connection work carried out by appropriately trained specialists only. ‣ Observe applicable federal/national installation codes and regulations. ‣...
Page 26
Electrical connection Proline 500 PROFIBUS PA Proline Promag P and Promag W E2 S2 41 42 37 36 n.c. n.c. n.c. 41 42 E1 E2 A0029145 Coil current cable Signal cable Connecting the connecting cable to the sensor connection housing Connection via terminals with order code for "Housing"...
Page 27
Proline 500 PROFIBUS PA Electrical connection Connecting the connecting cable to the transmitter 10 (0.4) 3 mm 22 mm 24 mm A0029592 Loosen the securing clamp of the connection compartment cover. Unscrew the connection compartment cover. Push the cable through the cable entry. To ensure tight sealing, do not remove the sealing ring from the cable entry.
Page 28
Electrical connection Proline 500 PROFIBUS PA 5.2.2 Connecting the signal cable and the supply voltage cable A0026781 Terminal connection for supply voltage Terminal connection for signal transmission, input/output Terminal connection for signal transmission, input/output or terminal connection for network connection via service interface (CDI-RJ45) Protective earth (PE) –...
Page 29
Proline 500 PROFIBUS PA Electrical connection N ic N ic t e r t e r e r g ö f f e r g ö f f iz e iz e t e n t e n r ir...
Electrical connection Proline 500 PROFIBUS PA 22 mm 24 mm – A0029816 10. Connect the cable in accordance with the terminal assignment . Signal cable terminal assignment: The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
Page 31
• Grounding rings can be ordered separately as an accessory from Endress+Hauser . When ordering make sure that the grounding rings are compatible with the material used for the...
Page 32
Electrical connection Proline 500 PROFIBUS PA Potential equalization via grounding electrodes on process connection A0028972 Hexagonal-headed bolts of process connection Integrated grounding electrodes O-ring seal Sensor 5.3.2 Promag P and Promag W For devices intended for use in hazardous locations, please observe the guidelines in the Ex documentation (XA).
Page 33
Proline 500 PROFIBUS PA Electrical connection Plastic pipe or pipe with insulating liner This connection method also applies in situations where: • The customary potential equalization is not used • Equalizing currents are present Ground cable Copper wire, at least 6 mm (0.0093 in...
Page 34
Electrical connection Proline 500 PROFIBUS PA Connect the measuring device to the power supply such that it is floating in relation to the protective ground (isolation transformer). Endress+Hauser...
Proline 500 PROFIBUS PA Electrical connection Hardware settings 5.4.1 Setting the device address The address must always be configured for a PROFIBUS DP/PA device. The valid address range is between 1 and 126. In a PROFIBUS DP/PA network, each address can only be assigned once.
Electrical connection Proline 500 PROFIBUS PA Software addressing ‣ To switch addressing from hardware addressing to software addressing: set DIP switch No. 4 to Off. The device address configured in the Device address parameter takes effect after 10 seconds. The device is restarted.
Proline 500 PROFIBUS PA Electrical connection To ensure that moisture does not enter the cable entry: Route the cable so that it loops down before the cable entry ("water trap"). A0029278 Insert dummy plugs into unused cable entries. Post-connection check Are cables or the device undamaged (visual inspection)? ...
Operation options Proline 500 PROFIBUS PA Operation options Overview of operation options A0034513 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370...
Proline 500 PROFIBUS PA Operation options Structure and function of the operating menu 6.2.1 Structure of the operating menu Operating menu for operators and maintenances Language Operation task-oriented Setup Diagnostics Operating menu for experts Expert function-oriented A0014058-EN 4 Schematic structure of the operating menu 6.2.2...
Operation options Proline 500 PROFIBUS PA Access to the operating menu via the local display X X X X X X 19.184 mA 12.5 X X X X X X Language 20.50 Ã English Deutsch Español Français Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W +0.000 Xx...
Page 41
Proline 500 PROFIBUS PA Operation options 6.3.1 Operational display Explanatory symbols for the measured value Status area • Depends on the device version, e.g.: The following symbols appear in the status area of the – : Volume flow operational display at the top right: –...
Page 42
Operation options Proline 500 PROFIBUS PA Numeric editor Confirms selection. Moves the input position one position to the left. Exits the input without applying the changes. Inserts decimal separator at the input position. Inserts minus sign at the input position.
Proline 500 PROFIBUS PA System integration Keys and meaning Minus/Enter key combination (press the keys simultaneously) With an operational display: • If keypad lock is active: Press the key for 3 s: Deactivates the keypad lock. • If keypad lock is not active: Press the key for 3 s: Opens the context menu including the option for activating the keypad lock.
Commissioning Proline 500 PROFIBUS PA Commissioning Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • "Post-installation check" checklist → 15 • "Post-connection check" checklist → 37 Setting the operating language...
Proline 500 PROFIBUS PA Diagnostic information Configuring the measuring device The Setup menu with its submenus and guided wizards is used for fast commissioning of the device. They contain all the parameters required for configuration, such as for measurement or communication.
Page 46
Diagnostic information Proline 500 PROFIBUS PA measures can be called up from the diagnostic message, and contains important information on the fault. X X X X X X X X X X X X X X 20.50 S801 Supply voltage...