Electrical Specifications; Electrical Outputs - Emerson Rosemount 935 Reference Manual

Open path combustible gas detector
Hide thumbs Also See for Rosemount 935:
Table of Contents

Advertisement

Technical specifications
May 2023
Per the requirements listed in the following performance standards:
EN 60079-29-4
Ansi/FM 60079-29-4
FM6325
5.2 

Electrical specifications

Operating Voltage:
5.2.1 
Typical Power consumption
Table 5-2: Transmitter and receiver typical power consumption
Receiver
Transmitter
5.2.2 
Electrical input protection
The input circuit is protected against voltage-reversed polarity, voltage transients, surges,
and spikes, according to EN50270.
5.3 

Electrical outputs

5.3.1 
0–20 mA current output
The 0–20 mA is an isolated Sink option. This output can also be configured as Transmitter
(see
Wiring
The maximum permitted load resistance is 600 Ω.
5.3.2 
Communication network
The receiver is equipped with RS-485 communication that can be used in installations with
computerized controllers.
Communication is compatible with the Modbus protocol:
This protocol is standard and widely used.
The protocol enables continuous communication between a single standard Modbus
controller (master device) and a serial network of up to 247 receivers.
The protocol enables connections between different types of Spectrex receivers or
other Modbus devices to the same network.
24
Hydrocarbon flames
Other external IR or UV radiation sources
Rain conditions or water spray
18-32 VDC
Without heated optic
85 mA
60 mA
configurations).
Reference Manual
00809-0100-4035
With heated optic
220 mA
240 mA
Emerson.com/Rosemount