Start-Up; Avoiding Slugging; Connection Of Oil Level Regulator - GEA HG22e/160-4 Assembly Instructions Manual

Table of Contents

Advertisement

6| Commissioning
Make sure that the suction and pressure line shut-off valves are open.
With the compressor switched off, add the liquid refrigerant directly to the condenser or receiver,
breaking the vacuum.
If the refrigerant needs topping up after starting the compressor, it can be topped up in vapour
form on the suction side, or, taking suitable precautions, also in liquid form at the inlet to the
evaporator.
ATTENTION

6.6 Start-up

WARNING
Check that the safety and protection devices (pressure switch, motor protection, electrical
contact protection measures, etc.) are all functioning properly.
Switch on the compressor and allow to run for a minimum of 10 min.
Check the oil level by: The oil must be visible in the sightglass.
ATTENTION I f larger quantities of oil have to be topped up, there is a risk of

6.7 Avoiding slugging

ATTENTION Slugging can damage the compressor and cause refrigerant to
To prevent slugging:
The complete refrigeration system must be properly designed.
All components must be compatibly rated with each other with regard to output
(particularly the evaporator and expansion valves).
Suction gas superheat at the compressor input should be min. 7 - 10 K. (check the setting
of the expansion valve).
The system must reach a state of equilibrium.
Particularly in critical systems (e.g. several evaporator points), measures are recommended such
as replacement of liquid traps, solenoid valve in the liquid line, etc.
There should be no movement of coolant whatsoever while the compressor is at a standstill.

6.8 Connection of oil level regulator

The connection "O" is provided for installing an oil level regulator. A corresponding adapter must be
obtained from the trade.
Avoid overfilling the system with refrigerant!
To avoid shifts in concentration, zeotropic refrigerant blends (e.g.
R407C) must always only be filled into the refrigerating plant in
liquid form.
Do not pour liquid coolant through the suction line valve on
the compressor.
It is not permissible to mix additives with the oil and refrigerant.
Ensure that both shut-off valves are open before starting the
compressor!
oil hammer effects.
If this is the case check the oil return!
leak.
D
GB
F
E
I
Ru
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hg34e seriesHg22e/125-4Hg22e/125-4 sHg22e seriesHg22e/160-4 sHg22e/190-4 ... Show all

Table of Contents