Cerabar M Analog
Endress+Hauser
5.1.2
Function of the operating elements
Operating key(s)
"Zero"
pressed briefly
"Zero"
pressed for at least 3 seconds
"Span"
pressed briefly
"Span"
pressed for at least 3 seconds
"Zero" and "Span" pressed together briefly Display position adjustment
"Zero" and "Span" pressed simultaneously
for at least 3 seconds
"Zero" and "Span" pressed simultaneously
for at least 12 seconds
5.2

Using the device display (optional)

A 4-line liquid crystal display (LCD) is used. The local display shows measured values, fault
messages and notice messages.
The display can be removed for easy operation (see diagram, steps 1 - 3). It is connected to the
device via a 90 mm (3.54 in) long cable.
The device display can be rotated in 90 ° stages (see diagram, steps 4 - 6).
Depending on the orientation of the device, this makes it easy to read the measured values.
1.
4.
Functions:
• 8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA as
current display.
• Diagnostic functions (fault and warning message etc.)
Meaning
Display lower range value
Get lower range value
The pressure present is accepted as the lower range value (LRV).
Display upper range value
Get upper range value
The pressure present is accepted as the upper range value (LRV).
Position adjustment
The sensor characteristic curve is shifted parallel to itself, so that the
pressure present becomes the zero value.
Reset
All parameters are reset to the order configuration.
2.
5.
Operation
3.
6.
P01-Mxxxxxxx-19-xx-xx-xx-011
25