Danfoss EKC 202B Manual page 6

Controller for temperature control
Hide thumbs Also See for EKC 202B:

Advertisement

Menu survey
Function
Normal operation
Temperature (set point)
Thermostat
Differential
Max. limitation of set point setting
Min. limitation of set point setting
Adjustment of temperature indication
Temperature unit (°C/°F)
Correction of the signal from Sair
Manual service(-1), stop regulation(0), start regulation (1)
Displacement of reference during night operation
Activation of reference displacement r40
Value of reference displacement (activation by r39 or DI)
Alarm
Delay for temperature alarm
Delay for door alarm
Delay for temperature alarm after defrost
High alarm limit
Low alarm limit
Alarm delay DI1
High alarm limit for condenser temperature (o70)
Compressor
Min. ON-time
Min. OFF-time
Compressor relay must cutin and out inversely (NC-function)
External relays (Zero crossing control – only EKC 302)
Must be 'ON' when connecting to external relays
Defrost
Defrost method (none/EL/gas)
Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Displacement of time on cutin of defrost at start-up
Drip off time
Delay for fan start after defrost
Fan start temperature
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
Defrost sensor (0=time, 1=S5, 2=Sair)
Max. aggregate refrigeration time between two defrosts
Defrost on demand - S5 temperature's permitted variation during frost build-up. On
central plant choose 20 K (=off )
Fans
Fan stop at cutout compressor
Delay of fan stop
Fan stop temperature (S5)
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
Six start times for defrost.
Setting of minutes.
0=OFF
Clock - Setting of hours
Clock - Setting of minute
Clock - Setting of date
Clock - Setting of month
Clock - Setting of year
Miscellaneous
Delay of output signals after start-up
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-pressure). 5=ext.main switch. 6=night operation
7=change reference (r40 will be activated) 8=alarm function when closed. 9=alarm func-
tion when open. 10=case cleaning (pulse pressure). 11=Inject off when open.
Network address
On/Off switch (Service Pin message)
Access code 1 (all settings)
Used sensor type (Pt /PTC/NTC)
Display step = 0.5 (normal 0.1 at Pt sensor)
Max hold time after coordinated defrost
Configuration of light function (relay 4)
1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows the DI-
function, when DI is selected to door function or to door alarm
Activation of light relay (only if o38=2)
6
Parameters
Manual RS8DZ702 © Danfoss 03-2012
Controller
EKC
EKC
EKC
Codes
202A /
202B
202C
302A
/302B
---
r01
r02
r03
r04
r05
r09
r12
r13
r39
r40
A03
A04
A12
A13
A14
A27
A37
c01
c02
c30
c70
d01
d02
d03
d04
d05
d06
d07
d08
d09
d10
d18
d19
F01
F02
F04
t01-t06
t11-t16
t07
t08
t45
t46
t47
o01
o02
o03
o04
o05
o06
o15
o16
o38
o39
EKC 202: SW = 1.3x
EKC 302: SW = 1.0x
Min.-
Max.-
Factory
Actual
value
value
setting
setting
-50°C
50°C
2°C
0,1 K
20 K
2 K
-49°C
50°C
50°C
-50°C
49°C
-50°C
-20 K
20 K
0.0 K
°C
°F
°C
-10 K
10 K
0 K
-1
1
1
-10 K
10 K
0 K
OFF
on
OFF
-50 K
50 K
0 K
0 min
240 min
30 min
0 min
240 min
60 min
0 min
240 min
90 min
-50°C
50°C
8°C
-50°C
50°C
-30°C
0 min
240 min
30 min
0°C
99°C
50°C
0 min
30 min
0 min
0 min
30 min
0 min
0 / OFF
1 / on
0 / OFF
OFF
On
On
no
gas
EL
0°C
25°C
6°C
0 hours
48 hours
8 hours
0 min
180 min
45 min
0 min
240 min
0 min
0 min
60 min
0 min
0 min
60 min
0 min
-15°C
0°C
-5°C
0
2
1
0
2
0
0 hours
48 hours
0 hours
0 K
20 K
20 K
no
yes
no
0 min
30 min
0 min
-50°C
50°C
50°C
0 hours
23 hours
0 hours
0 min
59 min
0 min
0 hours
23 hours
0 hours
0 min
59 min
0 min
1
31
1
1
12
1
0
99
0
0 s
600 s
5 s
0
11
0
0
240
0
OFF
ON
OFF
0
100
0
Pt
ntc
Pt
no
yes
no
0 min
60 min
20
1
3
1
OFF
ON
OFF
EKC 202 / 302