Fault message
In an error situation the LED's on the front will flash and the alarm relay will be activated. If you
push the top button in this situation you can see the alarm report in the display. If there are
further push again to see them.
There are two kinds of error reports - it can either be an alarm occurring during the daily opera-
tion, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired.
E-alarms, on the other hand, will become visible the moment the error occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear:
A1: High temperature alarm
A2: Low temperature alarm
A4: Door alarm
A5: Information. Parameter o16 is expired
A15: Alarm. Signal from DI input
A45: Standby position (stopped refrigeration via r12 or DI input)
A59: Case cleaning. Signal from DI input
A61: Condenser alarm
E1: Faults in the controller
E6: Fault in real-time clock. Check the battery / reset the clock.
E27: Sensor error on S5
E29: Sensor error on Sair
When copying settings to or from a copying key with functions o65 or o66, the following infor-
mation may appear:
0: Copying concluded and OK
4: Copying key not correctly mounted
5: Copying was not correct. Repeat copying
6: Copying to EKC incorrect. Repeat copying
7: Copying to copying key incorrect. Repeat copying
8: Copying not possible. Order number or SW version do not match
9: Communication error and timeout
10: Copying still going on
(The information can be found in o65 or o66 a couple of seconds after copying has been
started).
Warning ! Direct start of compressors *
To prevent compressor breakdown parameter c01 and c02 should be set according to suppliers requirements or in general :
Hermetic Compressors c02 min. 5 minutes
Semihermetic Compressors c02 min. 8 minutes and c01 min. 2 to 5 minutes ( Motor from 5 to 15 KW )
* ) Direct activating of solenoid valves does not require settings different from factory (0)
14
Manual RS8DZ702 © Danfoss 03-2012
Alarms
1 = alarm
High t. alarm
Low t. alarm
Door Alarm
Max Hold Time
DI1 alarm
Standby mode
Case cleaning
Cond. alarm
EKC error
-
S5 error
Sair error
Alarm destinations
The importance of the individual alarms
can be defined with a setting (0, 1, 2 or 3)