Danfoss EKC 202B Manual page 13

Controller for temperature control
Hide thumbs Also See for EKC 202B:

Advertisement

Copy the controller's present settings (EKC 202 only)
With this function the controller's settings can be transferred to a programming key. The key
can contain up to 25 different sets. Select a number. All settings except for Address (o03) will be
copied. When copying has started the display returns to o65. After two seconds you can move
into the menu again and check whether the copying was satisfactory.
Showing of a negative figure spells problems. See the significance in the Fault Message section.
Copy from the programming key (EKC 202 only)
This function downloads a set of settings earlier saved in the controller. Select the relevant
number.
All settings except for Address (o03) will be copied. When copying has started the display
returns to o66. After two seconds you can move back into the menu again and check whether
the copying was satisfactory. Showing of a negative figure spells problems. See the significance
in the Fault Message section.
Save as factory setting
With this setting you save the controller's actual settings as a new basic setting (the earlier fac-
tory settings are overwritten).
Other application for S5 sensor
Maintain the setting at 0 if the sensor has been defined as defrost sensor in D10. If D10 has been
set at 0 or 2 the S5 input can be used as product sensor or condenser sensor. Here you define
which:
0: Defrost sensor
1: Product sensor
2: Condenser sensor with alarm
Relay 4
Here you define the application for relay 4:
1: Defrost (EKC 202A / 302A) or Light (EKC 202C)
2: Alarm
Service
Temperature measured with S5 sensor
Status on DI input. on/1=closed
Status on night operation (on or off ) 1=night operation
Read the present regulation reference
* Status on relay for cooling
* Status on relay for fan
* Status on relay for defrost
* Temperature measured with Sair sensor
* Status on relay 4 (alarm, defrost or light function)
*) Not all items will be shown. Only the function belonging to the selected application can be
seen.
EKC 202 / 302
Manual RS8DZ702 © Danfoss 03-2012
o65
-
o66
-
o67
-
o70
S5 Config
o72
DO4 Config
- - - Night Setback
0=Day
1=Night
Service
u09
S5 temp.
u10
DI1 status
u13
Night Cond.
u28
Temp. ref.
u58
Comp1/LLSV
u59
Fan relay
u60
Def. relay
u69
Sair temp
u71
DO4 status