Operation Sequence Of The Burner; Burner Starting; Steady State Operation; Undesired Shutdown During Operation - Riello 1301 T Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burners
Table of Contents

Advertisement

6.11

Operation sequence of the burner

6.11.1 Burner starting

• 0s
: Thermostat/pressure switch TL closes.
Fan motor starts.
• 6s
: Motor starts. Servomotor starts: 130° rotation to right,
until contact is made on cam 1)
with light oil operation, or cam 4) with gas operation.
• 48s
The air gate valve is positioned on MAX. output.
Pre-purge stage with air delivery at MAX. output.
• 80s
: Servomotor rotates to left up to the angle set on cam
3).
with light oil operation, or cam 5) with gas operation.
• 109s : The air gate valve and the gas butterfly are positioned
to MIN. output.
• 113 s : Ignition electrode strikes a spark.
• 116s Pilot valve VP1 and VP2 open.
The flame is ignited at a low output level point A
(Fig. 41).
• 119 s :The spark goes out.
• 130s : Safety valve VS and adjustment valve VR (rapid
stroke) open.
Delivery is then progressively increased, with the
valve opening slowly up to MIN output, point B
(Fig. 41).
• 143s : The control box starting cycle ends.
TL
TR
M
VP1
VP2
VS
VR
M
20010305
Start-up, calibration and operation of the burner
NORMAL FIRING

6.11.2 Steady state operation

➤ Burner without output regulator RWF40
At the end of the starting cycle, the servomotor control then pass-
es to the thermostat/pressure switch TR for boiler pressure or
temperature point C (Fig. 41).
(The control box continues, however, to check that the flame is
present and that the air and gas max. pressure switches are in
the correct position).
If the temperature or pressure is low (and the thermostat/
pressure switch TR is consequently closed), the burner pro-
gressively increases its output to the MAX. value, (section C-
D).
If subsequently the temperature or pressure increases until
thermostat/pressure switch TR opens, the burner progres-
sively decreases its output to the MIN. value (section E-F).
And so on.
The burner locks out when demand for heat is less than the
heat supplied by the burner at min. output (section G-H).
Thermostat/pressure switch TL opens. The servomotor re-
turns to the 0° angle limited by contact with cam 2).
The gate valve closes completely to reduce thermal disper-
sion to a minimum.
Every time output is changed, the servomotor automatically mod-
ifies gas delivery (gas butterfly valve), air delivery (fan gate valve)
and air pressure (2 shutters in the combustion head).
➤ Burner with output regulator RWF40
See the handbook enclosed with the regulator.

6.11.3 Undesired shutdown during operation

If the flame should accidentally go out during operation, the burn-
er will lock out within 1s.

6.11.4 Firing failure

If the burner does not fire, it goes into lock-out within (Fig. 42) 3
s of the opening of the gas solenoid valve and 119 s after the
closing of control device TL.
TL
TR
M
VP1
VP2
D9333
VS
VR
Fig. 41
M
34
GB
D9334
Fig. 42

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 800/m mx20006817-3911112

Table of Contents