9.5.3 Main zone

EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1A – 2020.01
#
Code
[1.6]
[2-0A]
[1.7]
[2-09]
Overview
The following items are listed in the submenu:
2
Malfunctioning
Room

Main zone

Additional zone
Space heating/cooling
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]
Main zone.
See
"9.3.5 Setpoint
screen" [
Schedule
Indicate if the temperature of the leaving water is defined according to a schedule
or not.
Influence of the LWT setpoint mode [2.4] is as follows:
In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving
water temperatures, either preset or custom.
In Weather dependent LWT setpoint mode, the scheduled actions consist of
desired shift actions, either preset or custom.
Room sensor offset (Human Comfort
Interface (BRC1HHDA used as room thermostat)):
Offset on the actual room temperature measured
by the Human Comfort Interface.
–5°C~5°C, step 0.5°C
Room sensor offset (external room sensor
option): Only applicable if the external room
sensor option is installed and configured.
–5°C~5°C, step 0.5°C
[2] Main zone
Setpoint screen
[2.1] Schedule
[2.2] Heating schedule
[2.3] Cooling schedule
[2.4] Setpoint mode
[2.5] Heating WD curve
[2.6] Cooling WD curve
[2.7] Emitter type
[2.8] Setpoint range
[2.9] Control
[2.A] Thermostat type
[2.B] Delta T
[2.C] Modulation
[2.D] Shut off valve
[2.E] WD curve type
4
 116].
9
Configuration
|
Description
Installer reference guide