6 Electrical connection
6.1 Connection X1
2
1
3
6
4
5
7-pin plug, Binder, type 693
Pin
Pin 1
Uv, 24 V DC supply voltage
Pin 2
Uv GND
Pin 3
Relay output K1, common
Pin 4
Relay output K1, make contact
Pin 5
Relay output K2, common
Pin 6
Relay output K2, make contact
Pin PE
Function earth
6.2 Connection X2
2
1
5
3
4
5-pin M12 built-in socket, D-coded
Pin
Pin 1
Tx + (Ethernet)
Pin 2
Rx + (Ethernet)
Pin 3
Tx - (Ethernet)
Pin 4
Rx - (Ethernet)
Pin 5
Shield
6.3 Connection X3
2
3
1
8
4
7
5
6
8-pin M12 plug, A-coded
Pin
Pin 1
W+ set value input
Pin 2
W – set value input
Pin 3
X + actual value output
Pin 4
GND (actual value output, digital input 1 – 3, er-
ror message output)
Pin 5
Error message output 24 V DC
Pin 6
Digital input 3
Pin 7
Digital input 1
Pin 8
Digital input 2
GEMÜ 539 eSyDrive
Signal name
Signal name
Signal name
6.4 Connection X4
2
1
3
4
4-pin M12 built-in socket, A-coded
Pin
Pin 1
UV, 24 V DC actual value supply
Pin 2
n.c.
Pin 3
GND (actual value supply, actual value input)
Pin 4
X+, process actual value input
Pin 5
n.c.
6.5 Connecting the valve electrically
1. Protect the electrical connections from direct contact with
rain water.
2. Lay the cables and pipework so that neither condensate
nor rain water can get into the plug unions.
3. Check that all plug cable glands and fittings are mechanic-
ally secured.
ð The cable must be held firmly on all sides.
4. Check whether the actuator cover/manual override is
closed and undamaged.
5. Correctly close the actuator cover/manual override again
immediately after use (see chapter "Manual override" (see
"Manual override", page 29)).
6. Correctly close the product again after replacing the dia-
phragm (see chapter "Diaphragm replacement").
20 / 39