GEM 539 eSyDrive Operating Instructions Manual page 18

Motorized globe valve
Hide thumbs Also See for 539 eSyDrive:
Table of Contents

Advertisement

5 Technical data
5.7.5 Communication eSy-Web
Interface:
Function:
IP address:
Subnet screen:
The actuator and the PC must be in the same network to use the web server. The IP address of the actuator is entered in the
web browser and the actuator can then be parametrised. In order to use more than one actuator, a definitive IP address must be
assigned to each actuator in the same network.
5.7.6 Communication Modus TCP
Interface:
IP address:
Subnet screen:
Port:
Supported function
codes:
5.7.7 Behaviour in the event of an error
Function:
Error position:
GEMÜ 539 eSyDrive
Ethernet
Parameterisation via web browser
192.168.2.1 alterable via web browser
255.255.252.0 alterable via web browser
Modbus TCP
192.168.2.1 alterable via web browser
255.255.252.0 alterable via web browser
502
Code Dezimal
3
4
6
16
23
In the event of an error the valve moves to the error position.
Notes: Moving to the error position is only possible with full power supply. This behaviour is not a
safety position. The valve must be operated with a GEMÜ 1571 emergency power supply module
(see accessories) to ensure the function in case of voltage loss.
Closed, open or hold (adjustable via eSy-web web interface).
Code Hex
0x03
0x04
0x06
0x10
0x17
18 / 39
Function
Read Holding Registers
Read Input Registers
Write Single Register
Write Multiple Registers
Read / Write Multiple Registers
www.gemu-group.com