Mounting distance for panelled wall - combustible material
Fermacel 13
With convection above and below the stove
Convection area above the stove:
min 400 cm² (may be distributed).
Upper point of convection holes must
be min. 200 mm from combustible
material.
A
Convection area below the stove:
min. 300 cm² (may be distributed)
Distance to combustible material
min.
42
NB!!
Insulated chimney
down to the smoke
connector.
(not included)
B
B
A-A
400
Min.
mm
300
mm (e.g side wall)
RAIS - User manual for RAIS 900
B-B
A
100
Min.
mm
Convection hole below the
stove must be knocked out !!
400
Min.
mm
To guide the hot air out of the
gratings, install a non-combustible
plate with 30 mm fire batt on,
just above the holes.
Distance
375
min.
mm
Distance to furniture
900
min.
mm