Technibel MAFX96R5I/GRFX96R5I User Manual And Installation Manual page 21

Single-split air conditioner
Table of Contents

Advertisement

Piping hole
Model
Ø 55
Cooling capacity < 6000 W
Ø 70
Cooling capacity > 6000W
N.B.:
Take the necessary safety measures when
drilling the hole and do not allow dust to
enter.
The plastic wall plugs are not supplied but
must be purchased on site.
Step four: outlet pipe
The pipe can be brought out in various different
directions: right, rear right, left or rear left.
destra
destra
posterioredestra
sinistra
posterioresinistra
Step five: connect the indoor unit pipe
Position the
pipe joint in the corresponding
bellmouth.
Pre-tighten the union nut by hand.
Adjust the torque according to the following table. Position the open-end spanner on the pipe joint
and position the torque wrench on the union nut. Tighten the nut with the wrench.
chiave
dinamometrica
tubo interno
chiave a forchetta
chiavedinamometrica
tubointerno
dado raccordo
tubo
V 11/15
posteriore
sinistra
right
rear right
left
rear left
chiave
a forchetta
dado raccordo
tubo
open-end spanner
wrench
inner pipe
union nut
pipe
Once you have selected the direction of the
outlet (left or right), drill the corresponding
hole at the bottom.
sinistra
foro da
praticare
destra
foro da praticare
sinistra
giunto tubo
dado raccordo
giunto
tubo
dado
raccordo
Hex nut diameter
6.35
9.52
12.7
15.88
tuboisolante
Indoors
Outdoors
destra
right
hole to be drilled
left
tubo
pipe
joint
union
nut
Tightening torque (Nm)
15 – 20
30 – 40
45 – 55
60 – 65
tubo isolante
insulating tube
21