Riello RS 35/E BLU Installation, Use And Maintenance Instructions page 42

Forced draught gas burners
Table of Contents

Advertisement

Faults - Possible causes - Solutions
6
Error
Diagnostic
Meaning of the system REC27.100A2
code
code
98
#
Relay supervision error
2 Safety valve
3 Ignition
transformer
The relay does not start up
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
99 - 100 #
Relay internal checking error
105
#
Contact sampling internal error
0 Min. pressure
switch
1 Max.
pressure
switch
2 Valve
operation test
pressure
switch
3 Air pressure
4 Load
controller open
5 Load
controller on/
Blocked upon irregularity
off
6 Load
controller
closed
7 Safety loop /
Burner flange
8 Safety valve
9 Ignition
transformer
10 Fuel valve 1
11 Fuel valve 2
12 Fuel valve 3
13 Reset
106 - 108 #
Contact request internal error
110
#
Voltage monitoring test internal error
111
0
Low level of power supply
112
0
Reset power supply voltage
113
#
Mains voltage supervision internal error
115
#
Control box meter internal error
116
0
Life cycle of the control box in the critical interval
117
0
Life cycle of the control box exceeded
120
0
Interruption of fuel limiting meter input
121 - 124 #
EEPROM access internal error
125
#
EEPROM reading access internal error
126
#
EEPROM writing access internal error
127
#
EEPROM access internal error
EEPROM access internal error - synchronisation
128
0
during the initialisation
EEPROM access internal error – command
129
#
synchronisation
130
#
EEPROM access internal error - time-out
131
#
EEPROM access internal error - page interrupted
132
#
EEPROM register initialisation internal error
EEPROM access internal error – request
133 - 135 #
synchronisation
136
1
Restoration started
6372
Recommended measures
Carry out a reset; if the error arises repeatedly, replace the unit
Carry out a reset; if the error arises repeatedly, replace the control box
Can be caused by capacitive loads or presence of DC voltage on the main power
supply of the control box. The diagnostic code indicates the input in which the problem
arose
Carry out a reset; if the error arises repeatedly, replace the control box
Carry out a reset; if the error arises repeatedly, replace the control box
Insufficient mains voltage
Error code for the carrying out of a reset in the event of power supply restoration
(absence of error)
Carry out a reset; if the error arises repeatedly, replace the control box
The envisaged life cycle of the control box has been exceeded. Replace it.
The switch-off threshold has been reached.
Too many disturbance impulses on the input of the fuel meter.
Improve the electromagnetic compatibility.
Carry out a reset, repeat and check the last setting of the parameters. Restore the
group of parameters. If the error arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. Restore the
group of parameters. If the error arises repeatedly, replace the control box.
Carry out a reset; If the error arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
arises repeatedly, replace the control box.
Carry out a reset; If the error arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
arises repeatedly, replace the control box.
The restoration of a backup has been started (no error)
40
GB