Riello RS 35/E BLU Installation, Use And Maintenance Instructions page 38

Forced draught gas burners
Table of Contents

Advertisement

Parameter
No. par.
Description
Gas: Selection of flame sensor
221
0 = QRB.../ QRC
1 = ION / QRA
222
Gas: Selection of the pre-purging function
0 = deactivated
1 = activated
223
Maximum repeats of minimum gas pressure switch intervention
225
Gas: Pre-purging time
226
Gas: Pre-ignition time
230
Gas: Interval 1
232
Gas: Interval 2
233
Gas: Post-combustion time
234
Gas: Post-purging time
242
Gas: Emptying time (valve leak detection)
243
Gas: Atmospheric test time (valve leak detection)
244
Gas: Filling time (valve leak detection)
245
Gas: Pressure test time (valve leak detection)
261
Oil: Selection of flame sensor
0 = QRB.../ QRC...
1 = ION / QRA
265
Oil: Pre-purging time
266
Oil: Pre-ignition time
270
Oil: Interval 1
272
Oil: Interval 2
273
Oil: Post-combustion time
274
Oil: Post-purging time
281
Oil: Selection transformer ignition phase TA
0 = brief pre-ignition (Ph38)
1 = long pre-ignition (with fan) (Ph22)
400
Air / fuel modulation curve
401
Checking fuel servomotor
402
Checking air servomotor
500
Positioning of servomotors
501
Position of the fuel servomotor in absence of flame
Index 0 = standby position
Index 1 = pre-purging position
Index 2 = post-purging position
Number of
Unit of meas-
Modifica-
elements
urement
tion
1
-
Modification
1
-
Modification
1
-
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
-
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
s
Modification
1
-
Modification
13
(°)
Modification
13
(°)
Modification
3
(°)
Modification
Values interval
Degree of
precision
Min.
Max.
0
1
1
0
1
1
1
16
1
20 s
60 min
0.2 s
0.2 s
60 min
0.2 s
0.2 s
60 s
0.2 s
0.2 s
60 s
0.2 s
0.2 s
60 s
0.2 s
0.2 s
108 min
0.2 s
0.2 s
3 s
0.2 s
0.2 s
60 s
0.2 s
0.2 s
3 s
0.2 s
0.2 s
60 s
0.2 s
0
1
1
15 s
60 min
0.2 s
0.2 s
60 min
0.2 s
0.2 s
60 min
0.2 s
0.2 s
60 min
0.2 s
0.2 s
60 s
0.2 s
0.2 s
108 min
0.2 s
0
1
1
90°
0.1°
90°
0.1°
90°
0.1°
Predefined
Access mode
setting
1
Parameters Mode
1
Parameters Mode
16
Parameters Mode
20 s
Parameters Mode
2 s
Parameters Mode
2 s
Parameters Mode
2 s
Parameters Mode
8 s
Parameters Mode
0.2 s
Parameters Mode
3 s
Parameters Mode
10 s
Parameters Mode
3 s
Parameters Mode
10 s
Parameters Mode
0
Parameters Mode
15 s
Parameters Mode
2 s
Parameters Mode
2 s
Parameters Mode
2 s
Parameters Mode
8 s
Parameters Mode
0.2 s
Parameters Mode
0
Parameters Mode
0°; 0°; 15°; not
Parameters Mode
defined
0°; 90°; 45°; not
Parameters Mode
defined
0°; 0°; 15°
Parameters Mode

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 25/e blu878 t879 t

Table of Contents