Faults - Possible causes - Solutions
6
Error
Diagnostic
Meaning of the system REC27.100A2
code
code
137
#
Internal error – backup / restoration
Restoration – OK, but backup < compared with set data of
157
current system
242
Backup – the backup carried out is contradictory
Backup – the data comparison between the internal
243
microprocessors is irregular
244
The backup data are incompatible
245
Error in access to the parameter Restore_Complete
246
Restoration – time-out during logging in EEPROM
247
The data received are contradictory
248
The restoration cannot currently be carried out
Restoration – interruption caused by inadequate
249
identification of the burner
250
Backup – The CRC of a page is not correct
251
Backup – the identification of the burner is not defined
252
After restoration, the pages are still in INTERRUPTION
253
The restoration cannot currently be carried out
254
Interruption owing to transmission error
255
Interruption owing to time-out during the restoration
146
#
Time-out of the system automation interface
1
Modbus time-out
2
Reserved
165
#
Internal error
166
0
Watchdog reset internal error
167
#
Manual lockout
1
Manual lockout from remote reset command
2
Manual lockout from Operator Panel
3
Manual lockout from PC interface
168 - 171 #
Internal error management
200
#
System free of errors
201
#
Lockout or error at start
1
No operation mode selected
2..3
No fuel train defined
4..7
No curve defined
8..15
Standardisation speed not defined
16..31
Backup / restoration impossible
202
#
Selection of internal operation mode
203
#
Internal error
Phase
204
Program stop
number
205
#
Internal error
Combination of control box and Operator Panel not
206
0
allowed
207
#
Compatibility of control box with Operator Panel
0
Obsolete version of control box
1
Obsolete version of Operator Panel
208-209 #
Internal error
240
#
Internal error
245
#
Internal error
250
#
Internal error
Recommended measures
Restoration successful, but the backup data installed are fewer than those currently present in
the system.
The backup is irregular and cannot be transferred again
Repeat the reset and backup
The backup data are incompatible with the current version of the software; the
restoration is not possible
Repeat the reset and backup
Repeat the reset and backup
The series of backup data is not valid; restoration is not possible
Repeat the reset and backup
The backup has an inadequate identification of the burner and must not be transferred
to the control box
The series of backup data is not valid; restoration is not possible
Define the identification of the burner and repeat the backup
Repeat the reset and backup
Repeat the reset and backup
Repeat the reset and backup
Carry out a reset, check the connections and repeat the backup
Refer to the Modbus User Documentation (A7541)
The control box has been manually blocked (no error)
Carry out a reset; if the error arises repeatedly, replace the control box
No error
Lockout or error due to lack of parameter settings
Redefine the operation mode (parameter 201)
Redefine the operation mode (parameter 201)
Carry out a reset; if the error arises repeatedly, replace the control box
The program stop is active (no error)
Carry out a reset; if the error arises repeatedly, replace the control box
Carry out a reset; if the error arises repeatedly, replace the control box
Carry out a reset; if the error arises repeatedly, replace the control box
Carry out a reset; if the error arises repeatedly, replace the control box
Carry out a reset; if the error arises repeatedly, replace the control box
41
GB
6372