18.1.7 Piping length: VRV DX and Hydrobox

Installer and user reference guide
80
For system containing VRV DX indoor units and Hydrobox:
System setup
Example
Example 1
a
b
c
d
A
B
C
h
i
j
1
2
3
Example 2
a
H1
c
d
1
2
Example 3
a
b
c
d
1
2
3
1~7 VRV DX indoor units
8 Hydrobox unit (HXY080/125)
Maximum allowable length
Between outdoor and indoor units.
Actual piping length
(a)
Equivalent length
Total piping length
(a)
Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes of equivalent piping length, not for refrigerant charge calculations).
Maximum allowable height difference (on Hydrobox indoor unit)
H1
≤50 m (40 m) (if outdoor is located below indoor units)
H2
≤15 m
e
f
g
H1
D
E
F
G
p
k
l
m
n
4
5
6
7
8
H2
i
A
B
k
b
j
7
8
H2
e
f
g
h
3
4
5
6
H1
e
f
g
h
i
4
5
6
7
8
H2
135 m
Example 1:
a+b+c+d+e+f+g+p≤135 m
a+b+c+d+k≤135 m
Example 2:
a+i+k≤135 m
a+b+e≤135 m
Example 3:
a+i≤135 m
a+d≤135 m
160 m
300 m
Example 3:
a+b+c+d+e+f+g+h+i≤300 m
Description
Branch with refnet joint
Branch with refnet joint
and refnet header
Branch with refnet header
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10