Recommended Maintenance And Inspection; Recommended Maintenance And Inspection Cycles - Daikin VRV IV+ RYYQ14U7Y1B Series Installer And User Manual

Hide thumbs Also See for VRV IV+ RYYQ14U7Y1B Series:
Table of Contents

Advertisement

10
|
Maintenance and service

10.4.2 Recommended maintenance and inspection

10.4.3 Recommended maintenance and inspection cycles

Installer and user reference guide
38
If repairs to the product are necessary within the warranty period, contact your
dealer and keep the warranty card at hand.
Since dust collects when using the unit for several years, performance of the unit
will deteriorate to some extent. As taking apart and cleaning interiors of units
requires technical expertise and in order to ensure the best possible maintenance
of your units, we recommend to enter into a maintenance and inspection contract
on top of normal maintenance activities. Our network of dealers has access to a
permanent stock of essential components in order to keep your unit in operation
as long as possible. Contact your dealer for more information.
When asking your dealer for an intervention, always state:
The complete model name of the unit.
The manufacturing number (stated on the nameplate of the unit).
The installation date.
The symptoms or malfunction, and details of the defect.
WARNING
Do NOT modify, disassemble, remove, reinstall or repair the unit yourself as
incorrect dismantling or installation may cause an electric shock or fire. Contact
your dealer.
In case of accidental refrigerant leaks, make sure there are no naked flames. The
refrigerant itself is entirely safe, non-toxic and non-combustible, but it will
generate toxic gas when it accidentally leaks into a room where combustible air
from fan heaters, gas cookers, etc. is present. Always have qualified service
personnel confirm that the point of leakage has been repaired or corrected
before resuming operation.
Be aware that the mentioned maintenance and replacement cycles do not relate to
the warranty period of the components.
Component
Electric motor
PCB
Heat exchanger
Sensor (thermistor, etc.)
User interface and switches
Drain pan
Expansion valve
Solenoid valve
The table assumes the following conditions of use:
Normal use without frequent starting and stopping of the unit. Depending on the
model, we recommend not starting and stopping the machine more than 6
times/hour.
Operation of the unit is assumed to be 10 hours/day and 2,500 hours/year.
Inspection
Maintenance cycle
cycle
(replacements and/or repairs)
1 year
20,000 hours
25,000 hours
5 years
5 years
25,000 hours
8 years
20,000 hours
20,000 hours
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10