Huawei SUN2000-100KTL-M2 User Manual page 125

Hide thumbs Also See for SUN2000-100KTL-M2:
Table of Contents

Advertisement

SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual
Alarm
Alarm
ID
Name
2088
Abnorma
l DC
protectio
n unit
2093
Abnorma
l DC
Switches
Issue 07 (2023-04-30)
Alarm
Possible Cause
Severity
Major
● Cause ID = 1
The fuse is not in position or is
blown.
● Cause ID = 2
The two relays on the breaking
board are open-circuited.
● Cause ID = 3
The contact points of the DC
switches are stuck.
Minor
Cause ID=1
The DC switch is not in the ON
position, or the DC switch reset
button is not pressed down to the
bottom.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Suggestion
● Cause ID = 1/2
Turn off the AC output
switch and DC input
switch, and then turn
them on after 5 minutes.
Wait for the inverter to
connect to the power grid.
If the alarm persists after
5 minutes, contact your
dealer or technical
support.
● Cause ID = 3
If the PV indicator (LED1)
is off, contact your dealer
or Huawei technical
support to replace the
device. If the PV indicator
(LED1) is on, wait until the
PV string current
decreases to below 0.5 A.
Then turn off the AC
output switch and then
the DC input switch. After
5 minutes, turn on the AC
output switch and the DC
input switch. Wait until
the inverter connects to
the power grid. If the fault
persists after 5 minutes,
contact your dealer or
technical support for
replacement.
Check whether all DC
switches are in the ON
position. If not, turn the
switches to the ON position
(you can rotate the switches
with force to ensure that they
are in position). If the
switches still cannot be
turned to the ON position,
press the reset buttons of all
DC switches inwards until
they cannot be moved
further, and then turn on the
DC switches again.
118