Serial Port J3; Output Free Potential Contacts - GE Digital Energy SG Series Installation Manual

Hide thumbs Also See for Digital Energy SG Series:
Table of Contents

Advertisement

4.1.1 Serial Port J3

1
2
3
4
1
2
J3
3
4
Fig. 4.1.1-1 Serial port J3
The serial port J3 - RS232 is enabled
on all the units of the parallel system.

4.1.2 Output free potential contacts

The interface board provides 6 voltage free relay contacts giving some UPS critical alarms and
operation mode.
These signals are available either on connector J2- (sub D, female 25 pin) or terminal blocks X1.
The meaning of the alarms on the free contacts in standard configuration (default) is the following:
X1 / 1, 2, 3
X1 / 4, 5, 6
X1 / 7, 8, 9
X1 / 12, 13, 14
X1 / 15, 16, 17
X1 / 18, 19, 20
In case different alarms or operating status are required, they can be configured on the same terminals
via software from the control panel.
The configuration can be changed in parameters mode by a trained operator using the appropriate
password.
NOTE !
The programmable signals on X1 and J2 will be disabled with Q1 open, with the
exception of the signals for "16 - Manual Bypass ON" and "26 - EPO".
Modifications reserved
OPM_SGS_ISG_50K_80K_0US_V040.doc
Serial port J3 - RS-232 (sub D, female 9 pin) that allows:
Total remote management of the system using new generation software
JUMP (Java Universal Management Platform) for system protection and
management of systems using GE UPS.
JUMP system is written in JAVA and supports virtually all platforms having
"JAVA runtime environment".
or
J2 / 1, 2, 3
or
J2 / 4, 5, 6
J2 / 7, 8, 9
or
or
J2 / 14, 15, 16
or
J2 / 17, 18, 19
or
J2 / 20, 21, 22
Fig. 4.1.1-2 Serial port J3 connection to PC with RS232 1:1 cable DB9m – DB9f
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
Utility Failure
Load on Inverter
Stop Operations
Load on Utility
General Alarm
Acoustic Alarm
Page 35/38
Installation Guide SG Series 50 & 80 kVA

Advertisement

Table of Contents
loading

Table of Contents