Product Description; Function; Interfaces; Marking - Pepperl+Fuchs KFD0-SD2-Ex2.1 45 Series Manual

Solenoid driver
Table of Contents

Advertisement

Functional Safety KFD0-SD2-Ex2.1*45

Product Description

2
Product Description
2.1

Function

This isolated barrier is used for intrinsic safety applications.
The device supplies power to solenoids, LEDs and audible alarms located in a hazardous
area.
It is loop powered, so the available energy at the output is received from the input signal.
The output signal has a resistive characteristic. As a result the output voltage and current
are dependent on the load and the input voltage.
2.2

Interfaces

The device has the following interfaces.
Safety relevant interfaces: input 1, input 2, output 1, and output 2
Non-safety relevant interfaces: none
Note
For corresponding connections see datasheet.
2.3

Marking

Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
KFD0-SD2-Ex2.1045, KFD0-SD2-Ex2.1245, KFD0-SD2-Ex2.1545
2.4

Standards and Directives for Functional Safety

Device specific standards and directives
Functional safety
System-specific standards and directives
Functional safety
8
IEC/EN 61508, part 1 – 7, edition 2010:
Functional safety of electrical/electronic/programmable electronic
safety-related systems (manufacturer)
IEC 61511-1:2016+COR1:2016+A1:2017
EN 61511-1:2017+A1:2017
Functional safety – Safety instrumented systems for the process
industry sector (user)
Up to SIL 3