Functional Safety KFD0-SD2-Ex2.1*45
Planning
3.2

Assumptions

The following assumptions have been made during the FMEDA:
Failure rate based on the Siemens standard SN 29500.
Failure rates are constant, wear is not considered.
The safety-related device is considered to be of type A device with a hardware
fault tolerance of 0.
Only one input and one output are part of the safety function (only for 2-channel version).
The device will be used under average industrial ambient conditions comparable
to the classification stationary mounted according to MIL-HDBK-217F.
Alternatively, operating stress conditions typical of an industrial field environment similar
to IEC/EN 60654-1 Class C with an average temperature over a long period of time
of 40 ºC may be assumed. For a higher average temperature of 60 ºC, the failure rates
must be multiplied by a factor of 2.5 based on experience. A similar factor must be used
if frequent temperature fluctuations are expected.
SIL 3 Application
To build a SIL safety loop for the defined SIL, it is assumed as an example that this device
uses 10 % of the available budget for PFD
For a SIL 3 application operating in low demand mode the total PFD
of the SIF (Safety Instrumented Function) should be smaller than 10
hence the maximum allowable PFD
For a SIL 3 application operating in high demand mode the total PFH value
of the SIF should be smaller than 10
would then be 10
Since the safety loop has a hardware fault tolerance of 0 and it is a type A device,
the SFF must be > 90 % according to table 2 of IEC/EN 61508-2 for a SIL 3 (sub) system.
3.3

Safety Function and Safe State

Safe State
The safe state of the output is the de-energized state. The output current is less than 50 A.
Safety Function
When the input signal is active, the output is activated. The safe state is introduced
when the input voltage is below 5 V DC.
Reaction Time
The reaction time for all safety functions is < 1 s.
Note
See corresponding datasheets for further information.
10
avg
value would then be 10
avg
-7
per hour, hence the maximum allowable PFH value
-8
per hour.
/PFH.