Solenoid driver

Advertisement

Quick Links

Functional Safety
Solenoid Driver
KFD2-SLD-Ex2.1*45
Manual
3
ISO9001

Advertisement

Table of Contents
loading

Summary of Contents for Pepperl+Fuchs SIL KFD2-SLD-Ex2.1 45 Series

  • Page 1 Functional Safety Solenoid Driver KFD2-SLD-Ex2.1*45 Manual ISO9001...
  • Page 2 Phone: +49 621 776 - 0 E-mail: info@de.pepperl-fuchs.com North American Headquarters Pepperl+Fuchs Inc. 1600 Enterprise Parkway Twinsburg, Ohio 44087 Phone: +1 330 425-3555 E-mail: sales@us.pepperl-fuchs.com Asia Headquarters Pepperl+Fuchs Pte. Ltd. P+F Building 18 Ayer Rajah Crescent Singapore 139942 Phone: +65 6779-9091 E-mail: sales@sg.pepperl-fuchs.com https://www.pepperl-fuchs.com...
  • Page 3: Table Of Contents

    Functional Safety KFD2-SLD-Ex2.1*45 Contents Introduction ............5 Content of this Document .
  • Page 4 Functional Safety KFD2-SLD-Ex2.1*45 Contents...
  • Page 5: Introduction

    Additionally, the following parts may belong to the documentation, if applicable: • EU-type examination certificate • EU declaration of conformity • Attestation of conformity • Certificates • Control drawings • FMEDA report • Assessment report • Additional documents For more information about Pepperl+Fuchs products with functional safety, see www.pepperl-fuchs.com/sil.
  • Page 6: Safety Information

    Functional Safety KFD2-SLD-Ex2.1*45 Introduction Safety Information Target Group, Personnel Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator. Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product. The personnel must have read and understood the instruction manual and the further documentation.
  • Page 7: Symbols Used

    Functional Safety KFD2-SLD-Ex2.1*45 Introduction Symbols Used This document contains symbols for the identification of warning messages and of informative messages. Warning Messages You will find warning messages, whenever dangers may arise from your actions. It is mandatory that you observe these warning messages for your personal safety and in order to avoid property damage.
  • Page 8: Product Description

    Safety relevant interfaces: input 1, input 2, output 1, and output 2 • Non-safety relevant interfaces: fault indication output Note For corresponding connections see datasheet. Marking Pepperl+Fuchs Group Lilienthalstraße 200, 68307 Mannheim, Germany Internet: www.pepperl-fuchs.com KFD2-SLD-Ex2.1045, KFD2-SLD-Ex2.1245, KFD2-SLD-Ex2.1545 Up to SIL 3 Standards and Directives for Functional Safety...
  • Page 9: Planning

    Functional Safety KFD2-SLD-Ex2.1*45 Planning Planning System Structure 3.1.1 Low Demand Mode of Operation If there are two control loops, one for the standard operation and another one for the functional safety, then usually the demand rate for the safety loop is assumed to be less than once per year.
  • Page 10: Assumptions

    Functional Safety KFD2-SLD-Ex2.1*45 Planning Assumptions The following assumptions have been made during the FMEDA: • Failure rate based on the Siemens standard SN 29500. • Failure rates are constant, wear is not considered. • External power supply failure rates are not included. •...
  • Page 11: Safety Function And Safe State

    Functional Safety KFD2-SLD-Ex2.1*45 Planning Safety Function and Safe State Safe State The safe state of the output is the de-energized state. The output current is less than 0.5 mA. Safety Function When the input signal is active, the output is activated. The safe state is introduced when the input voltage is below 5 V DC.
  • Page 12: Characteristic Safety Values

    Functional Safety KFD2-SLD-Ex2.1*45 Planning Characteristic Safety Values KFD2-SLD-Ex2.1*45 without LFT (SIL3) in 1oo1 Structure Parameters Characteristic values Assessment type and Full assessment documentation Device type Mode of operation Low demand mode oder high demand mode Safety function Output is de-energized 181 FIT ...
  • Page 13 Functional Safety KFD2-SLD-Ex2.1*45 Planning KFD2-SLD-Ex2.1*45 with LFT (SIL2) in 1oo1 Structure Parameters Characteristic values Assessment type and Full assessment documentation Device type Mode of operation Low demand mode oder high demand mode Safety function Output is de-energized 183 FIT  0 FIT ...
  • Page 14: Useful Lifetime

    As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the manufacturer and plant operator can extend the useful lifetime. Our experience has shown that the useful lifetime of a Pepperl+Fuchs product can be higher if the ambient conditions support a long life time, for example if the ambient temperature is significantly below the maximum ambient temperature.
  • Page 15: Mounting And Installation

    Functional Safety KFD2-SLD-Ex2.1*45 Mounting and Installation Mounting and Installation Mounting and Installing the Device Observe the safety instructions in the instruction manual. Observe the information in the manual. Observe the requirements for the safety loop. Connect the device only to devices that are suitable for this safety application. Check the safety function to ensure the expected output behavior.
  • Page 16: Operation

    Functional Safety KFD2-SLD-Ex2.1*45 Operation Operation Danger! Danger to life from missing safety function If the safety loop is put out of service, the safety function is no longer guaranteed. • Do not deactivate the device. • Do not bypass the safety function. •...
  • Page 17 Functional Safety KFD2-SLD-Ex2.1*45 Operation Proof Test Procedure Prepare a test set-up, see figure below. Test the devices in the mode of operation they are used in. If necessary, change the configuration of the device. Verify the input and output values as given in table below.
  • Page 18: Maintenance And Repair

    Report all failures in the safety function that are due to functional limitations or a loss of device function – especially in the case of possible dangerous failures. In these cases, contact your local sales partner or the Pepperl+Fuchs technical sales support (service line).
  • Page 19: List Of Abbreviations

    Functional Safety KFD2-SLD-Ex2.1*45 List of Abbreviations List of Abbreviations Emergency Shutdown Failure In Time in 10 Failure Mode, Effects, and Diagnostics Analysis FMEDA Probability of safe failure  Probability of dangerous detected failure  Probability of dangerous undetected failure  Probability of failures of components in the safety loop that have ...
  • Page 20 Pepperl+Fuchs Quality Download our latest policy here: www.pepperl-fuchs.com/quality www.pepperl-fuchs.com © Pepperl+Fuchs · Subject to modifications DOCT-8081A...