Trane Voyager TS 150-300 Series Installation, Operation And Maintenance Manual page 49

Packaged rooftop air conditioners
Hide thumbs Also See for Voyager TS 150-300 Series:
Table of Contents

Advertisement

MWU and DWU setpoints come from the higher
priority LCI-R DAC.
Table 14. Variable air volume mode operation
System Mode
DWU Active
Heat
DWU Off
Cool
DWU Active
Auto
DWU Off
Off
Notes:
1. If Cooling is selected the supply fan will run continuously. If VAV
Heating is activated the supply fan will run continuously.
2. If Daytime Warmup is Activated, the supply fan will run
continuously.
3. Auto changeover between Cooling and Daytime
Warmup depends upon the DWU initiate setpoint.
4. The fan will be Off any time the system selection switch
is "Off".
Supply Duct Static Pressure Control
The supply duct static pressure is measured by a
transducer with a 0.25 to 2.125 Vdc proportional output
which corresponds to an adjustable supply duct static
pressure of 0.3" w.c. to 2.5" w.c. respectively with a
deadband adjustment range from 0.2" w.c. to 1.0" w.c. The
setpoint is adjustable on the RTAM Static Pressure
Setpoint potentiometer or through ICS.
Example:
Supply Duct Static setpoint = 2.0" w.c. (RTAM)
Deadband = 0.2" w.c. (RTAM)
Duct Static Control Range = 1.9" w.c. to 2.1" w.c.
Mechanical Cooling with an Economizer
The economizer is utilized to control the zone temperature
when the outside air conditions are suitable. The method
used to determine economizer effectiveness, depending
on the available data, is described below in descending
order of complexity.
Table 15. Economizer effectiveness
Method used to determine
economizer effectiveness
Comparative Enthalpy
Reference Enthalpy
Reference Dry Bulb
Unable to determine effectiveness
The most sophisticated method available is always used.
Two of the three methods for determining the suitability of
the outside air can be selected utilizing the potentiometer
on the Economizer Actuator, as described below:
1. Ambient Temperature - controlling the economizing
cycle by sensing the outside air dry bulb temperature.
RT-SVX25Q-EN
Fan "Auto"
Fan "On"
2
2
DWU
DWU
4
4
Off
VAV Heating
1
1
VAV Cooling
VAV Cooling
DWU or
DWU or
1,2,3,4
Cooling
1,2,3,4
Cooling
VAV Cooling or
1
VAV Cooling
1
Heating
4
4
Off
Off
Required
OAT, OAH, RAT, RAH
OAT, OAH
OAT
OAT data is invalid or
unavailable
Table 16
lists the selectable dry bulb values by
potentiometer setting.
2. Reference Enthalpy - controlling the economizer cycle
by sensing the outdoor air humidity.
selectable enthalpy values by potentiometer setting. If
the outside air enthalpy value is less than the selected
value, the economizer is allowed to operate.
Table 16. Economizer configuration
Selection
Dry Bulb
A
73°F
B
70°F
C
67°F
D
63°F
E
55°F
3. Comparative Enthalpy - By utilizing a humidity sensor
and a temperature sensor in both the return air stream
and the outdoor air stream, the economizer will be able
to establish which conditions are best suited for
maintaining the zone temperature, i.e., indoor
conditions or outdoor conditions.
Off Mode
This mode is set at the zone sensor or by ICS. During this
status, no heating, ventilation, or mechanical cooling is
being performed. When switching the "System" selector
to the "Off" mode from any other mode, any diagnostic
data and diagnostic indication signal will be retained as
long as the system remains in the "Off" status. Switching
the "System" selector from the "Off" mode back to any
other mode of operation will reset all diagnostics.
Heating Operation
Heating operation on units configured with Traditional
Multi-Zone VAV control will utilize two separate control
methodologies based on heating configurations. For all
"Staged" Heating types, the unit will utilize 100% full
airflow during all active heating periods like traditional
Constant Volume units. If the unit has modulating heat, the
unit can be made to do discharge heating with VAV control.
This is done by placing by placing a contact closure across
the "Changeover Input" on the RTAM. During this mode,
the unit will heat to the Supply Air Heating Setpoint ± 3.5°F.
During low load or low airflow conditions the actual
temperature swing of the discharge air will likely be
greater.
Zone Temperature - Unoccupied Heating
While a building is in an unoccupied period as designated
by a remote panel with night setback or ICS, the necessary
heating capacity will be controlled to maintain the zone
temperature to within the unoccupied setpoint deadband.
For traditional VAV systems, the VFD will operate at 100%
during this mode. It will be necessary to drive VAV boxes
to their maximum position through ICS programming or
the factory provided VHR relay. For all Staged Heating
Sequence of Operation
Table 16
lists the
Enthalpy Value
27 BTU/LB Air
25 BTU/LB Air
23 BTU/LB Air
22 BTU/LB Air
19 BTU/LB Air
49