Powered and Unpowered
Convenience
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with a CAT III or IV
voltmeter rated per NFPA 70E that all capacitors have
discharged.
Figure 19. Wiring schematic 12½ through 25 ton options
RT-SVX25Q-EN
Factory-Mounted Unit Options
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury.
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state/national electrical codes.
Powered Convenience Outlet Powered
Option (FIYCOPO)
When the powered convenience outlet option is installed,
the unit will include a dedicated transformer located in the
evaporator section of the unit. Additionally, a service
receptacle disconnect switch will be provided on the side
wall of the evaporator section. The service receptacle
switch is shipped in the OFF position.
The powered outlet comes completely wired from the
factory except for 208 volt applications.
1. For 208 volt applications, disconnect and tape the blue
230 volt wire.
2. Then connect the brown 208 volt wire.
31