30 Complete the start guide
Here you select whether to start the start guide the next
time the heat pump is restarted.
Caution
If you choose "yes" this means that the next
time the heat pump is started (e.g. after a power
cut) it will not produce heat or hot water for 60
minutes.
NIBE™ F1126

Post adjustment and venting

Pump capacity diagrams, collector side
To set the correct flow in the brine system the correct
speed must be set for the brine pump.
The flow must have a temperature difference between
brine out (BT11) and brine in (BT10) of 2 - 5 °C when the
system is balanced (suitably 5 minutes after compressor
start). Check these temperatures in menu 3.1 "service
info" and adjust the brine pump (GP2) speed until the
temperature difference is achieved. A high difference in-
dicates a low brine flow and a low difference indicates a
high brine flow.
Read off what speed the brine pump should have from
the diagrams below.
Tillgängligt tryck
Eleffekt
P
F1126 6 kW
Tillgängligt tryck, kPa
80
70
60
50
40
30
20
10
0
0
0,05
0,1
0,15
0,2
Chapter 6 |
Eleffekt, W
160
140
P3
P2
120
P1
100
3
80
2
60
40
1
20
Flöde
0
0,25
0,3
0,35
0,4
l/s
Commissioning and adjusting