Maytag Amana MVM97 Series Installation Instructions Manual page 28

Modulating gas furnace, fsp category iv direct or non direct vent air furnace

Advertisement

C
M
I
OUNTERFLOW
ODEL
NSTALLED
S
D
IDE
OWN
Minimum 5 1/2" clearance is required for the drain trap
beneath the furnace.
*Also see Front Cover Pressure Switch Tube Location on
page 14.
Hose #4
1. Remove the factory installed drain trap and hose
assemblies. Leave the 100°elbow inserted and
clamped in the vent drain elbow.
2. Remove two 1"plugs from left side of cabinet
3. (Draining the Collector Box) Remove the cap from
the left side of the collector box drain port (bottom
in horizontal left position) and install it on right side
drain port.
4. Place radius end of hose #4 (factory installed) on the
collector box drain port and secure with a silver clamp.
5. Insert hose #2 from outside the cabinet in the front
drain hole.
6. Connect hose #4 & hose #2 together using a straight
barbed coupling and two gold clamps (factory installed).
7. (Draining the Vent Elbow) Remove rubber plug from
vent – drain elbow side port.
8. The unused vent-drain elbow drip leg port must be
plugged to prevent flue gases from escaping. Insert
rubber plug removed in step 7 into the 100° elbow..
(Inserting a blunt tool such as a 3/16'' Allen wrench
into the center of the rubber plug will stretch the plug
and allow complete insertion)
9. Place radius end of hose #4 on the side port of vent –
drain elbow and secure with a gold clamp.
10. Insert a ½" diameter PVC pipe (factory installed) into
hose #4 and secure with a gold clamp.
11. Insert the non-grommet end of hose #5 (factory
installed) from outside the cabinet in the back drain
hole.
28
H
ORIZONTALLY WITH
Hose #4
Hose #5
Hose #2
Figure 30
L
12. Insert 100º elbow in hose #5 and secure with a red
EFT
clamp.
13. Locate hose #4 and cut a cut off a 4" straight section
and discard the radius end.
14. Connect the 4" straight section of hose #4 to the 100º
elbow and the PVC pipe and secure with red clamps.
15. Connect the hoses to the trap inlets and secure with
silver clamps, drain trap outlet must point to the
original bottom of the furnace.
16. Using the two sheet metal screws provided in the
cabinet, secure the trap to the furnace.
17. Refer to Field Supplied Drain section for instructions
on field supplied / installed drain on outlet of
furnace trap.
E
C
LECTRICAL
HIGH VOLTAGE !
T
O AVOID THE RISK OF ELECTRICAL SHOCK
THE UNIT MUST BE POLARIZED AND GROUNDED
HIGH VOLTAGE !
T
O AVOID PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK
BEFORE SERVICING OR CHANGING ANY ELECTRICAL
.
WIRING
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
. W
CONTROLS
IRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
. V
OPERATION
ERIFY PROPER OPERATION AFTER SERVICING
W
H
IRING
ARNESS
The wiring harness is an integral part of this furnace. Wires
are color coded for identification purposes. Refer to the
wiring diagram for wire routings. If any of the original wire
as supplied with the furnace must be replaced, it must be
replaced with wiring material having a temperature rating
of at least 105° C. Any replacement wiring must be a copper
conductor.
115 V
L
OLT
INE
Before proceeding with electrical connections, ensure that
the supply voltage, frequency, and phase correspond to that
specified on the unit rating plate. Power supply to the fur-
nace must be NEC Class 1, and must comply with all appli-
cable codes. The furnace must be electrically grounded in
accordance with local codes or, in their absence, with the
latest edition of The National Electric Code, ANSI NFPA 70
and/or The Canadian Electric Code CSA C22.1.
ONNECTIONS
WARNING
,
WIRING TO
.
WARNING
,
DISCONNECT ELECTRICAL POWER
CAUTION
C
ONNECTIONS
.