Samson TROVIS SAFE 3730-6 Series Mounting And Operating Instructions page 118

Electropneumatic positioner with hart communication and pressure sensors
Hide thumbs Also See for TROVIS SAFE 3730-6 Series:

Advertisement

Operating the positioner
7.8.1
Selecting the type of application
If the type of application 'On/off valve' is not set or you want to change it to the type of ap-
plication 'Control valve', proceed as follows:
Enable configuration:
Configuration is locked again if no settings are entered within 120 s.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Select the type of application:
1. Turn
until Code 49 appears.
2. Press
, the code number 49 blinks.
3. Turn
until Code h0 appears.
4. Press
, the code h0 blinks.
5. Turn
and select parameter: YES (on/off valve) or No (control valve)
6. Press
to confirm.
118
Enable configuration
Default: No
EB 8384-6S EN