Download Print this page

Nibe F1345 Service Manual page 20

Ground source heat pump
Hide thumbs Also See for F1345:

Advertisement

5 Component description
Compressor (GQ10)
Size
24
30
40
60
Other components
Component
Reversing valve
(QN10)
Heating medium
pump (GP1)
20
Chapter 5 |
Component description
Type
T1-T3[C-R]
Scroll
3.64
Scroll
2.52
Scroll
2.08
Scroll
1.52
Description
Actuator motor: 7 VA, 230/24 VAC, 50 Hz, IP 40. Running time approx 8 sec.
Max. operating pressure: 1.0 MPa
Operating temperature: 5 - 80 °C (90 °C briefly)
24 - 60 kW
Max lift height: 7.5 m
Control signal: PWM 0-10 V DC (max-min speed)
Resistance range (Ω at 20 °C +/- 10 %)
T1-T2[C-S]
3.64
2.52
2.08
1.52
(94)
Ø28
T2-T3[S-R]
3.64
2.52
2.08
1.52
F1345

Advertisement