SECTION 4 – INITIAL START-UP
4.4.2 PROPANE GAS COMBUSTION CALIBRATION
PROPANE Combustion Calibration Instructions
These instructions apply only to units running PROPANE gas. Instructions for doing
combustion calibration on a unit running Natural Gas appear in the previous section, 4.4.1.
1.
Open the water supply and return valves to the unit and ensure that the system pumps are
running.
2.
Open the
PROPANE
3.
Set the C-More Controller's ON/OFF switch to the OFF position
4.
Turn on external AC power to the unit. The display will show a description of the unit and
then the time and date.
5.
Press the MENU key on the front panel of the C-More Controller and access the Setup
menu, enter the password 6817 and then press the ENTER key.
6.
Set the unit to the MANUAL mode by pressing the AUTO/MAN key. A flashing Manual
Valve Position message will be displayed with the present position in % and the MANUAL
LED will light.
Adjust the air/fuel valve position to 0% by pressing the ▼ arrow key and then press
7.
ENTER.
8.
Ensure that the leak detection ball valve downstream of the SSOV is open and the
manometer is attached and functioning properly.
9.
Set the ON/OFF switch to the ON position.
10.
Press the MENU key on the front panel of the C-More Controller until COMBUSTION CAL
MENU appears on the display.
Press the Up ▲ arrow key until SET Stdby V Out (Standby Voltage) setting appears.
11.
Verify that it is set to 2.0 V (the default). AERCO recommends it be kept at 2.0 volts to
prevent flue gas recirculation. Individually vented units in positive pressure boiler rooms
may set SET Stdby V Out to 0 volts.
Press the Down ▼ arrow key until SET Valve Position appears, then press CHANGE.
12.
Use the Up ▲ arrow key to change the valve position to 30%. The unit should begin its
13.
start sequence and fire.
14.
Next, verify that the gas pressure downstream of the SSOV is set to the value in Table 4-4
for the model you are calibrating. If gas pressure adjustment is required, remove the brass
hex nut on the SSOV actuator to access the gas pressure adjustment screw (Figure 4-3).
Make gas pressure adjustments using a flat-tip screwdriver to obtain a gas pressure
approximately shown in Table 4-4.
TABLE 4-4: PROPANE Gas Pressure Range @ 100% Fire Rate
Model
BMK 750P
BMK 1000P
1500DF & 1500P
2000DF & 2000P
2500DF & 2500P
3000DF & 3000P
15.
On Benchmark 3000 units only, once the manifold gas pressure is within the range in
table 4-1, record this value; it will be used later, in Section 5.2.2: Low Pressure Gas Test,
and Section 5.3.2: High Pressure Gas Test.
OMM-0121_D • GF-205 • 5/9/2019
supply valve to the unit.
Nominal Gas Pressure
3.9" W.C. ± 0.2" W.C. (0.97 kPa ± 0.05 kPa)
7.6" W.C. ± 0.2" W.C. (1.89 kPa ± 0.05 kPa)
1.4" W.C. ± 0.1" W.C. (0.35 kPa ± 0.02 kPa)
2.5" W.C. ± 0.1" W.C. (0.62 kPa ± 0.02 kPa)
2.0" W.C. ± 0.1" W.C. (0.50 kPa ± 0.02 kPa)
1.6" W.C. ± 0.1" W.C. (0.40 kPa ± 0.02 kPa)
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST