3.3
ELECTRICAL CONNECTIONS TO THE BURNER TERMINAL STRIP
H
Remote lock-out signal
IN
Optional switch on-off burner
MB Burner terminal strip
PS
Reset push - button
SA High temperature oil alarm
NOTE:
Check the lock-out by darkening the flame sensor after removal of the cover.
ATTENTION HIGH VOLTAGE.
In case of supply 230V without neutral, connect the motor and the pre-heater thank through delta (the "star"
connection is the original one, made for 400V).
NOTE 
In systems where the run of wiring connecting the thermostat exceeds 20 metres in length, or in places where
the burner is subject to particularly disturbing electromagnetic interference (over 10 v/m), you must insert the
relay-interface kit item number 3010386.
2915844
DIRECT START-UP
(to be carried out by the installer)
TL
Limit control device system
TS
Safety control device system
T2
Load control system for 2
Load control system for 3
T3
9
GB
D2619
230V
400V
A A gG/gL
63
50
B A gG/gL
63
50
2
C mm
6
4
2
D mm
10
6
nd
stage
rd
stage