Installation

2.2 NAC Circuit Wiring

2.2.1 Class B
The standard configuration for NACs is Class B as shown below. Use Listed ELRs supplied by the FACP or compatible equipment manufac-
turer.
2.2.2 ZNAC-PS Class A Option Module
The ZNAC-PS is an optional Class A conversion module which mounts to connector J8 on the upper right side of the circuit board. This
module allows the HPF-PS6 or HPF-PS10 to support Class A Notification Appliance Circuits on all outputs. Class A power supervision is
also supported on output circuits #1 and #2 when either of these outputs are configured as resettable or non-resettable auxiliary power.
ZNAC-PS SW1 and SW2 settings must match the HPF-PS output 1 and 2 settings to ensure proper supervision.
Two slide switches are located on the right side of the ZNAC-PS module to properly configure output circuits #1 and #2 for either NAC or
Auxiliary Power operation, as described below. Note that there are no slide switches for the remaining outputs as these outputs do not sup-
port Class A power supervision.
For output #1, set the upper switch to either "NAC1" or "AUX1" depending on the intended operation.
For output #2, set the lower switch to either "NAC2" or "AUX2" depending on the intended operation.
NOTE: Class A supervision and the ZNAC-PS module are not intended for use with door holder operation.
14
Alarm Polarity Shown
Figure 2.2 NAC Class B
ZNAC-PS Option Module
Figure 2.3 Class A NACs using ZNAC-PS Option Module
HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022
2k-27kΩ ELR
-
Horn Strobe
+
-
Horn Strobe
+
-
Horn Strobe
+
-
+
-
+
-
+
Horn Strobes
-
+
-
+
TB8
-
+
ZNAC-PS
NAC1
AUX1
NAC2
AUX2
HPF-PS Circuit Board
NAC Circuit Wiring
HPF-PS Circuit Board
Alarm
Polarity
Shown