Benchmark Alpha E-Tec Plus 28 Installation And Servicing Instruction page 51

Wall mounted, fan assisted, room sealed, gas fired, high efficiency condensing combination boiler
Table of Contents

Advertisement

Error
Fault
code
Service reminder
Sr
Boiler completely
n
turned off
Boiler fused blown
Fault description
Service reminder count down (0 - 36 months)
has reached zero
See Section 6.13, parameter P6
Note: E97 is also shown on Climatic controller,
if used
Screen only shows a single dot to indicate
boiler is completely off
Fuse on main PCB blown
Alpha E-Tec Plus 28, 33 and 38 - Error Codes and Fault Finding
Possible causes
Note: The 'Sr' code will not stop the boiler
functioning
Note: Pressing the RESET button will clear the
'Sr' code for 24 hrs to allow the display to be
read
To permanently reset the error 'Sr' / E97
1. Enter the parameter menu using the
password 69. See Section 6.13
2. Parameter P6 will show 0
3. Set P6 to any value above zero, save by
pressing the mode button (
for '88' to be displayed as confirmation
4. Then set P6 to 0, save by pressing the mode
button (
) and wait for '88' to be
displayed as confirmation
5. Now set the parameter P6 at the number
of months to the next service reminder
(i.e. 12 for one year). Save by pressing the
mode button (
) and wait for '88' to be
displayed as confirmation
Press mode button (
) for 2 seconds then
release. Boiler display will return and you can
select an operating mode
Incorrect power supply.
Seized or sticking pump - Check pump for free
rotation
Boiler component drawing excessive current.
Check individual components in turn
) and wait
51