6.6.15.5 Setting low pressure detection (KIWA)

The minimum pressure switch that detects low pressure can be connected to any input (for electrical connections,
refer to paragraph 2.3.3).
The low pressure detecting function is obtained by setting the parameter Ix, for the input to which the enabling signal
has been connected, on one of the values in Tabella 26.
Activation of the low pressure detection function generate a system block after time T1 (see T1: Tempo di
spegnimento dopo il segnale bassa pressione par. 6.6.2). This function is envisaged to connect the input to a signal
from a pressure switch that indicates excessively low pressure on pump intake.
When this function is enabled, the symbol F4 is shown on the STATUS line of the main page.
When in the F4 error condition, the input must be deactivated for at least 2 seconds before the system unblocks. The
function behaviour is summarised in Table 26.
When several low pressure detection functions are configured at the same time on different inputs, the system
indicates F4 when at least one function is activated and clears the alarm when none are activated.
Response of system enable and fault reset function according to setting of INx and input
Parameter
value
INx
10
11
12
13

6.6.16 Setup of outputs OUT1, OUT2

This section illustrates the functions and possible configurations of the outputs OUT1 and OUT2 via parameters O1
and O2.
For electrical connections, see par. 2.3.4.
The default settings are those in Table 27.

6.6.16.1 O1: Output 1 function setting

Output 1 notifies of an active alarm (i.e. that there is a system block). The output enables use of a normally closed or
normally open voltage-free contact.
Parameter O1 is associated with the values and functions specified in Table 28.

6.6.16.2 O2: Output 2 function setting

Output 2 notifies of electric pump running status (pump on/off). The output enables use of a normally closed or
normally open voltage-free contact.
Parameter O2 is associated with the values and functions specified in Table 28.
Input
Input status
configuration
Active with high
signal on input
(NO)
Active with low
signal on input
(NC)
Active with high
signal on input
(NO)
Active with low
signal on input
(NC)

Table 26: Low pressure signal detection (KIWA)

Default output settings
Output
OUT 1
OUT 2

Table 27: Default output settings

ENGLISH
Operation
Absent
System block due to low
Present
pressure on intake;
automatic + manual reset
System block due to low
Absent
pressure on intake;
automatic + manual reset
Present
Absent
System block due to low
Present
pressure on intake.
Manual reset
System block due to low
Absent
pressure on intake.
Manual reset
Present
Value
2 (fault NO closes)
2 (Pump running NO closes)
86
Normal
Normal
Normal
Normal
Display
None
F4
F4
None
None
F4
F4
None