46/71
Bosch Rexroth AG
Instructions for Use
Tightening Torque
5.2.11

Ground Connection

5.2.12

Shield Connection

XS1, Shield Connection Control Lines

HMV01.1E-W0030, -W0075
HMV01.1R-W0018, -W0045, -W0065
HMV02.1R-W0015
6 Nm
Fig.5-25:
Tightening Torque
The ground connection of the housing is used to provide functional safety of
the drive controllers and protection against contact in conjunction with the
equipment grounding conductor.
Ground the housings of the drive controllers:
1. Connect the bare metal back panel of the drive controller in conductive
form to the mounting surface in the control cabinet. To do this, use the
supplied mounting screws.
2. Connect the mounting surface of the control cabinet in conductive form
to the equipment grounding system.
3. For the ground connection, observe the maximum allowed ground re‐
sistance.
See Project Planning Manual of the drive system (index entry "Mains
connection → Project planning").
NOTICE
Observe the indicated minimum distances!
Above the devices there may only be such materials which
are not combustible
are insensitive to the occurring high temperatures
Always connect the shields with the largest possible metal-to-met‐
al contact surface.
DOK-INDRV*-HMV02******-IT01-EN-P
Rexroth IndraDrive Supply Units HMV02
HMV01.1E-W0120
HMV01.1R-W0120
18 Nm
Property damage due to temperatures higher
than 105 ℃!