9 Technical data
e
Heat sink PCB
f
Pressure regulating valve
g
Heat exchanger
h
Service port (high pressure)
i
Muffler
j
Check valve
k
Compressor accumulator
l
Capillary tube
m
Service port (refrigerant charge)
n
Accumulator
M1C
Compressor
M1F
Fan motor
R1T
Thermistor (air)
R2T
Thermistor (discharge)
R3T
Thermistor (suction 1)
R4T
Thermistor (heat exchanger de-icer)
R5T
Thermistor (suction 2)
R6T
Thermistor (subcool heat exchanger)
R7T
Thermistor (liquid pipe)
S1NPH
High pressure sensor
S1NPL
Low pressure sensor
S1PH
High pressure switch
Y1E
Electronic expansion valve (main)
Y3E
Electronic expansion valve (subcool heat exchanger)
Y1S
Solenoid valve (4‑way valve)
Heating
Cooling
9.3

Wiring diagram: Outdoor unit

The wiring diagram is delivered with the unit, located at the inside of
the service cover.
Notes for RXYSCQ4~6:
1
This wiring diagram applies only to the outdoor unit.
2
Symbols (see below).
3
Refer to the installation manual for how to use the BS1~BS5
and DS1+DS2 switches.
4
When operating, do not short-circuit protective device S1PH.
5
Colours (see below).
6
Refer to the installation manual for connection wiring to
INDOOR-OUTDOOR transmission F1-F2.
7
When using the central control system, connect OUTDOOR-
OUTDOOR transmission F1-F2.
Symbols:
L
Live
N
Neutral
Field wiring
Terminal strip
Connector
Fixed connector
Movable connector
Protective earth (screw)
Noiseless earth
Terminal
Colours:
BLK
Black
BLU
Blue
BRN
Brown
GRN
Green
ORG
Orange
RED
Red
Installation and operation manual
24
WHT
White
YLW
Yellow
Legend for wiring diagram RXYSCQ4~6:
A1P
Printed circuit board (main)
A2P
Printed circuit board
BS1~BS5
Push button switch
C1
Capacitor
DS1
DIP switch
E1HC
Crankcase heater
F1U
Fuse
F3U, F4U
Fuse (T 6.3 A / 250 V)
F6U
Fuse (T 5.0 A / 250 V)
H1P~H8P
Light‑emitting diode (service monitor orange)
H2P:
▪ Prepare, test: Flickering
▪ Malfunction detection: Light up
HAP
Light-emitting diode (service monitor is green)
HBP
Light-emitting diode (service monitor is green)
K11M
Magnetic contactor
K1R
Magnetic relay (Y1S)
K4R
Magnetic relay (E1HC)
K10R
Magnetic relay
L1R~L3R
Reactor
M1C
Motor (compressor)
M1F
Motor (fan)
PS
Switching power supply
R1, R2
Resistor
R1T
Thermistor (air)
R2T
Thermistor (discharge)
R3T
Thermistor (suction 1)
R4T
Thermistor (heat exchanger de-icer)
R5T
Thermistor (suction 2)
R6T
Thermistor (subcool heat exchanger)
R7T
Thermistor (liquid pipe)
FINTH
Thermistor (fin)
S1NPH
High pressure sensor
S1NPL
Low pressure sensor
S1PH
High pressure switch
V1R
IGBT power module
V2R
Diode module
V1T~V3T
Insulated gate bipolar transistor (IGBT)
V1D~V3D
Diode
X1M, X2M
Terminal strip
X37A
Connector
Y1E
Electronic expansion valve (main)
Y3E
Electronic expansion valve (subcool heat exchanger)
Y1S
Solenoid valve (4‑way valve)
Z1C~Z7C
Noise filter (ferrite core)
Z1F~Z5F
Noise filter
RXYSCQ4~6TMV1B
VRV IV-S system air conditioner
4P555881-1 – 2019.07