Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP select
LED
Signaling
Group signaling contact (NO
contact)
14
and group signaling contact
Off
Lights up
green
Lights up red
Flashes red
Light up red
Flashes red
6EP1961-2BA00
All LEDs:
No supply voltage
Device powering up: After the device has powered up, the outputs
are switched on, taking into consideration the switch-on delay that
has been set.
Normal operation, output is switched on
Output switched off automatically to due overload
Outputs ready to be reset after an automatic switch off by pressing the
button
All LEDs are red (after actuating the reset button for a minimum of
8 s):
programming mode for the switch-on delay
All LEDs flash red (in the programming mode):
signals the programmed switch-on delay time:
all LEDs flash 1x simultaneously red, followed by a 2 s pause:
0 ms
all LEDs flash 2x simultaneously red, followed by a 2 s pause:
24 ms
all LEDs flash 3x simultaneously red, followed by a 2 s pause:
100 ms
Signal contact 13-14 opens (=quiescent position) when one/several
outputs are switched off as a result of overload or when a fuse rup-
tures.
Selectivity modules
Manual, 12.2014, C98130-A7579-A1-1-7629