York AFFINITY YAFT026 Installation Manual page 71

Geothermal heat pumps single and dual capacity
Hide thumbs Also See for AFFINITY YAFT026:
Table of Contents

Advertisement

Troubleshooting cont.
Single Speed/Dual Capacity Startup/Troubleshooting Form
1. Job Information
Model #
Serial #
2. Flow Rate in gpm
WATER IN Pressure:
WATER OUT Pressure:
Pressure Drop: a - b
Look up flow rate in table:
3. Temp. Rise/Drop Across Coaxial Heat Exchanger
WATER IN Temperature:
WATER OUT Temperature:
Temperature Difference:
4. Temp. Rise/Drop Across Air Coil
SUPPLY AIR Temperature:
RETURN AIR Temperature:
Temperature Difference:
5. Heat of Rejection (HR)/Heat of Extraction (HE)
Brine Factor
:
2
HR/HE = d x g x k
STEPS 6-9 NEED ONLY BE COMPLETED IF A PROBLEM IS SUSPECTED.
6. Watts
Volts:
Total Amps (Comp. + Blower)
:
3
Watts = m x n x 0.85:
7. Capacity
Cooling Capacity = l - (o x 3.413):
Heating Capacity = l + (o x 3.413):
8. Efficiency
Cooling EER = p / o:
Heating COP = p / (o x 3.413):
9. Superheat (S.H.)/Subcooling (S.C.)
Suction Pressure:
Suction Saturation Temperature:
Suction Line Temperature:
S.H. = t - s
Head Pressure:
High Pressure Saturation Temp:
Liquid Line Temperature
:
4
S.C. = w - x
NOTES:
Steps 3-9 should be conducted with the hot water generator disconnected.
1
Use 500 for pure water, 485 for methanol or Environol™. (This constant is derived by multiplying the weight of one gallon of water (8.34) times the minutes
2
in one hour (60) times the specific heat of the fluid. Water has a specific heat of 1.0.
If there is only one source of power for the compressor and blower, amp draw can be measured at the source wiring connection.
3
Liquid line is between the coax and the expansion device in the cooling mode; between the air coil and the expansion device in the heating mode.
4
AFFINITY & AFFINITY ADVANCED SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
Job Name:
Install Date:
SOURCE COAX
HEATING
a.
psi
a.
b.
psi
b.
c.
psi
c.
d.
gpm
d.
1
HEATING
e.
°F
e.
f.
°F
f.
g.
°F
g.
SOURCE COAX
HEATING
h.
°F
h.
i.
°F
i.
j.
°F
j.
k.
HEATING
l.
Btu/h
l.
ENERGY MONITOR
HEATING
m.
Volts
m.
n.
Amps
n.
o.
Watts
o.
HEATING
p.
Btu/h
p.
HEATING
q.
Btu/h
q.
HEATING
r.
psi
r.
s.
°F
s.
t.
°F
t.
u.
°F
u.
v.
psi
v.
w.
°F
w.
x.
°F
x.
y.
°F
y.
COOLING
HEATING
psi
a.
psi
b.
psi
c.
gpm
d.
COOLING
HEATING
°F
h.
°F
i.
°F
j.
COOLING
°F
°F
°F
COOLING
Btu/h
COOLING
Volts
Amps
Watts
COOLING
Btu/h
COOLING
Btu/h
COOLING
psi
°F
°F
°F
psi
°F
°F
°F
71
Loop: Open / Closed
Hot Water Generator: Y / N
LOAD COAX (Water-to-Water)
COOLING
psi
a.
psi
b.
psi
c.
gpm
d.
LOAD COAX (Water-to-Water)
COOLING
°F
h.
°F
i.
°F
j.
Software Version
ABC:
AXB:
IZ2:
T'STAT:
psi
psi
psi
gpm
°F
°F
°F