omron E3K-R10K4 wiring for max pro
UL325-2018
NORMALLY CLOSED (NC)
Wiring to E3K Photocell
NOTE: To meet the UL 325 2018 standard,
Type B1 Non-Contact sensor entrapment
protection device MUST be MONITORED
by the gate operator.
Installation Steps:
1. Set switch to "LIGHT ON"
Wire 12V power to photocell
2.
Wire OPEN ONLY NC
3.
to photocell NO2
Wire GND to photocell C2
4.
Align photocell to reflector
5.
Adjust sensitivity
OPEN ONLY
NC
PHOTO CLS
NC
OPEN/CLS
NC
12VDC OUT
GND
OPEN ONLY
10K
CLS ONLY
10K
OPEN/CLS
10K
12VDC OUT
GND
For 10K Resistor E3K Photocell wiring see next page
OPENING Direction
Photocell (Reflector)
UL 2018 Label on packaging
Set switch to
"LIGHT ON"
LIGHT ON
DARK ON
Min
Max
SENSITIVITY
Sensitivity Adjustment:
If the photocell does not respond to an
obstruction, lower the sensitivity by
turning adjustment counter-clockwise.
DO NOT
connect
to NC2 #4.
Power
C-1 NO1 NC1
NC2 N02 C2
1 2
3
4
5 6
24 to 240 VAC
24 to 240
N02 C2
OPEN ONLY NC
12VDC Out Monitored
GND
Polarity does NOT matter
IMPORTANT:
Photocell MUST be powered
by 12VDC OUT Monitored or
it will NOT be MONITORED.
UL325-2018
NORMALLY CLOSED (NC)
Wiring to E3K Photocell
NOTE: To meet the UL 325 2018 standard,
Type B1 Non-Contact sensor entrapment
protection device MUST be MONITORED
by the gate operator.
Installation Steps:
1. Set switch to "LIGHT ON"
Wire 12V power to photocell
2.
Wire PHOTO CLS NC
3.
to photocell NO2
Wire GND to photocell C2
4.
Align photocell to reflector
5.
Adjust sensitivity
VDC
OK to
use
12VDC
OPEN ONLY
P
P
P
P
PHOTO CLS
OPEN/CLS
12VDC OUT
OPEN ONLY
CLS ONLY
OPEN/CLS
12VDC OUT
For 10K Resistor E3K Photocell wiring see next page
23
UL 325 2018 Standard - MAX 1200 FS PRO/1700 FS PRO Matrix III Install Version 2c
CLOSING Direction
Photocell (Reflector)
UL 2018 Label on packaging
Set switch to
"LIGHT ON"
LIGHT ON
Min
Max
SENSITIVITY
Sensitivity Adjustment:
If the photocell does not respond to an
obstruction, lower the sensitivity by
turning adjustment counter-clockwise.
DO NOT
connect
to NC2 #4.
C-1 NO1 NC1
NC2 N02 C2
1 2
3
4
N02 C2
NC
PHOTO CLS NC
NC
NC
12VDC Out Monitored
GND
GND
Polarity does NOT matter
10K
10K
10K
IMPORTANT:
Photocell MUST be powered
GND
by 12VDC OUT Monitored or
it will NOT be MONITORED.
DARK ON
Power
5 6
24 to 240 VAC
24 to 240 VDC
OK to
use
12VDC