5.6 Recommended excess air when
using default setting
Grade of gas
Natural gas
Propane
Butane
Liquefied petroleum
gas (LPG)
5.7 Determining the gas quantity for
the system
The heat values indicated are normal values; the heat value varies according
to the origin of the gas. For more exact information on values, contact the
gas distributor.
Lower heat value Hu at normal state 15°C and 1013.25 mbar EN676
Grade of gas
Natural gas
G20
Natural gas
G25
Propane
G31
Butane
G30
Excess air flue gases
% O
% CO
Lambda 1.2
2
2
3–5
≈10
3–5
≈11.5
3–5
≈11,5
3–5
≈11
kWh/Nm
3
MJ/Nm
3
9.5
34.02
8.2
29.25
24.6
88.00
32.5
116.09
Max. % CO
2
11.9
13.9
14,1
13,8
kcal/Nm
3
8126
6986
21019
27728
172 515 26
2018-01-11
27