SMC Networks HRR030-A-20 Series Operation Manual page 84

Hide thumbs Also See for HRR030-A-20 Series:
Table of Contents

Advertisement

HRX-OM-W002
Chapter 5 Display and Setting of Various Functions
Setting for electric conductivity rise alarm
9.
Press the [▼] key. Displays screen for setting value of electric conductivity rise alarm
threshold.
Displayed only when Option DM is selected [Electrical conductivity control function , DI
water (pure water) piping].
RUN
The user can change the threshold of "AL12
Setting range
:0.4 to 46.0 µS/cm(
Setting of NOT TEMP READY alarm
10.
Press the [▼] key. Displays screen for changing the chiller behaviour when the NOT
TEMP READY alarm occurs.
RUN
The user can decide the chiller behaviour if alarm "AL13: NOT TEMP READY" occurs.
Set value
OFF
WRN
FLT
5.5 Advanced setting mode
5-36
El ectric conductivity rise alarm threshold
Initial value
Operation at occurrence of NOT TEMP READY alarm
TEMP ⇒READY ⇒ ALARM( Alternately displayed )
Contents
Alarm is not generated.
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the
alarm occurs.
."
electric conductivity rise
:45.0 µS/cm)
unit
:µS/cm
Initial value
HRR Series