Start-Up, Calibration And Operation Of The Burner; Notes On Safety For The First Start-Up; Combustion Adjustment; Nozzles Installation - Riello 40 B I0 Operation Instructions Manual

Kerosene and gas oil burner
Table of Contents

Advertisement

8

Start-up, calibration and operation of the burner

8.1

Notes on safety for the first start-up

The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
tions of the laws in force.
WARNING
8.2

Combustion adjustment

In conformity with Efficiency Directive 92/42/EEC the application
of the burner on the boiler, adjustment and testing must be car-
ried out observing the instruction manual of the boiler, including
verification of the CO and CO
their temperatures and the average temperature of the water in
the boiler.
Nozzle
GPH
0.40
0.50
0.60
0.65
0.65
0.50
0.60
0.65
0.75
0.85
1.00
8.3

Nozzles installation

The burner complies with the emission requirements of the
EN 267 standard.
In order to guarantee that emissions do not vary, recommended
and/or alternative nozzles specified by the manufacturer in the In-
struction and warning booklet should be used.
It is advisable to replace nozzles every year dur-
ing regular maintenance operations.
WARNING
The use of nozzles other than those specified by
the manufacturer and inadequate regular mainte-
nance may result into emission limits non-con-
forming to the values set forth by the regulations
in force, and in extremely serious cases, into po-
tential hazards to people and objects.
CAUTION
The manufacturing company shall not be liable for
any such damage arising from nonobservance of
the requirements contained in this manual.
20035148
Start-up, calibration and operation of the burner
concentration in the flue gases,
2
Angle
80°/60°
60°
60°
60°
60°
60°
60°
60°
60°
60°
60°
Check the correct working of the adjustment, com-
mand and safety devices.
WARNING
To suit the required appliance output, fit the nozzle then adjust
the pump pressure and the air damper opening in accordance
with the Tab. E.
Pump pressure
bar
12
12
12
12
13
8
8
8
8
8
8
8.3.1

Nozzles reccomended

Monarch
type R - NS
Delavan
type W - A - E
Steinen
type H - Q
Danfoss
type H - B
Angle 60°: in most cases.
Angle 80°: in case of flame detachment, during ignitions at low
temperatures.
18
GB
Burner
Air damper
output
adjustment
kg/h ± 4%
Set-point
1.72
2.15
2.58
2.79
2.91
1.5
1.8
1.9
2.2
2.5
3.0
1.95
2.2
2.8
3.2
3.7
1.5
1.75
2.1
2.5
3.0
4.0
Tab. E

Advertisement

Table of Contents
loading

This manual is also suitable for:

G3b437t5020030780

Table of Contents