Securing the burner to the boiler

Provide an adequate lifting system.
Separate the combustion head from the rest of the burner, as
shown in Fig. 11.
To do this, proceed as follows:
 loosen the four screws 3) and remove the hood 1);
 disengage the articulated coupling 7) from the graduated
sector 8);
D8688
If the probe or electrode is not correctly positioned, you must:
 remove the screw 1)(Fig. 12);
 take out the inner part 2)(Fig. 12) of the head, and then cali-
brate them.
Once this operation (if necessary) has been carried out, fix the
flange 11)(Fig. 11) to the boiler plate, interposing the insulating
gasket 9)(Fig. 11) supplied.
Use the 4 screws supplied, with a tightening torque of 35 - 40 Nm,
after protecting their thread with anti-seizing products.
The seal between burner and boiler must be air-
tight: after the start-up, check there is no leakage
of flue gases into the external environment.
WARNING
20054100
Installation
 remove screws 2) from the two slide bars 5);
 remove the 2) screws 4) and pull the burner back on slide
 disconnect the probe and electrode cables, then slide off the
WARNING
11
10
1
2
5
16
GB
bars 5) by about 100mm;
burner completely from the slide bars.
Before fixing the burner to the boiler, check
(through the opening of the blast tube) that the
probe and electrode are correctly positioned (see
Fig. 13).
15
15
6
1
2
D8689
14
13
12
9
8
3
7
4
3
Fig. 11