6.5.3
Minimum gas pressure switch
Adjust the minimum gas pressure switch (Fig. 33) after perform-
ing all the other burner adjustments with the pressure switch set
to the start of the scale.
With the burner operating at maximum output, increase adjust-
ment pressure by slowly turning the relative knob clockwise until
the burner stops.
Now turn the knob anticlockwise by 2 mbar and repeat burner
start-up to ensure it is uniform.
If the burner locks out again, turn the knob anticlockwise again by
1 mbar.
6.5.4
PVP pressure switch kit
Adjust the pressure switch for the leak detection control (PVP
kit)(Fig. 34) according to the instructions supplied with the kit.